background image

 

GAMMA  instabus

 

Technical Product Information 

August 2013 

Binary input device N 262E01 

5WG1 262-1EB01

 

8x potential-free contacts  

Siemens AG 

N 262E01, 4 pages 

Technical Manual

 

Infrastructure & Cities Sector, Building Technologies  

 

Control Products and Systems 

 Siemens AG 2013 

Update: http://www.siemens.com/gamma

 

P.O. Box 10 09 53, D-93009 Regensburg 

Subject to change without further notice 

 

 

2.7.3.2/1 

Product and function description 

 

 

 

 

The  N  262E01  binary  input  device  is  a  6  module  units  
wide DIN rail mounted device in N-System dimensions 
with 8 inputs for potential-free contacts. It enables both 
statuses (contact is open or closed) and changes in status 
(contact became opened or closed) to be recorded by 
means of voltage impulses generated inside of the de-
vice.  It  can  therefore  be  used,  for  example,  to  monitor  
the switching or operating states (whether a device or a 
plant is switched on or off, whether a limit violation or a 
malfunction or an alarm is being signalled), to record the 
change of status when switching on or switching off 
(whether a switch or a pushbutton was activated, 
whether it was activated for a shorter or longer period) 
and to record and count changes of the switching status 
(i.e. pulses) with a minimum on-time of the contact of 70 
ms and a max. pulse succession of up to 5 pulses per 
second, without or with monitoring of the number of 
pulses counted until a predetermined threshold has been 
reached or exceeded. 
At each input a red LED shows whether the connected 
contact is open (LED is off) or closed (LED is illuminated). 
The N 262E01 has an integrated 230 V power supply in 
order to supply the electronics. This power supply en-
ables the generation of the voltage pulses for checking 
the switching statuses and for displaying them via the 
LEDs even when there is no bus voltage present. 
Note: The device is without function after the application 
program has been “unloaded” with the ETS. The status of 
the inputs is also no longer displayed in this case. 

 
 

Application program 

 

The “25S8 Binary Input Device 980903” application pro-
gram,  which  can  be  downloaded  up  from  the  ETS3.0f,  

supports a multitude of applications and enables one of 
the following functions to be assigned to every input: 
-

 

Switching status / binary value transmission 

-

 

Switching, edge-triggered 

-

 

Switching, short / long operation 

-

 

1-button dimming 

-

 

1-button solar protection control 

-

 

1-button group control (sequence control) 

-

 

1-bit Scene control 

-

 

8-bit Scene control 

-

 

8-bit value, edge-triggered 

-

 

8-bit value, short / long operation 

-

 

16-bit floating point value, edge-triggered 

-

 

16-bit floating point value, short / long operation 

-

 

8-bit pulse counting without threshold check 

-

 

8-bit pulse counting with threshold check 

-

 

16-bit pulse counting without threshold check 

-

 

16-bit pulse counting with threshold check 

-

 

32-bit pulse counting without threshold check 

-

 

32-bit pulse counting with threshold check. 

 

Using the ETS, one of the following functions can be al-
located  to  one  input  pair,  i.e.  to  two  neighbouring  in-
puts: 
-

 

2-button dimming with stop telegram 

-

 

2-button solar protection control. 

 
 

Connection example 
 

 

in

s

ta

b

u

s

  

E

IB

N 262E01

     

B

u

s

 c

o

u

p

lin

g

 u

n

it

A

B

C

D

E

G

H

Eingang
Input

A

B

C

D

E

G

H

230 V AC

 

Содержание 262E01

Страница 1: ...nnected contact is open LED is off or closed LED is illuminated The N 262E01 has an integrated 230 V power supply in order to supply the electronics This power supply en ables the generation of the voltage pulses for checking the switching statuses and for displaying them via the LEDs even when there is no bus voltage present Note The device is without function after the application program has be...

Страница 2: ...age and displaying normal mode addressing mode 1 green LED for displaying the 230 V operating voltage 1 red LED per binary input for status display LED ON contact is closed Inputs 8 inputs potential free with basic insulation 250 V against each other and against the EIB Detection of the switching status of a floating contact connected to an input by means of voltage pulses gen erated by the device...

Страница 3: ...conductor and neutral conductor N for power supply of the electronics A7 LED for displaying the operating voltage Installation and wiring General description The DIN rail mounted device in N system dimensions width 6 module units can be inserted in N system dis tribution boards surface or flush mounted and wher ever DIN rails according to EN 60715 TH35 7 5 are pre sent Installing the DIN rail moun...

Страница 4: ...ct system must be covered using the supplied insulating cap Removing the locating clamp Figure 4 The locating clamp E3 encloses the contact system E2 on the rear of the device E1 Insert the screwdriver between the DIN rail mounted device E1 and the locating clamp E3 and remove the clamp Clipping on the insulating cap Figure 4 Place the insulating cap E4 on the contact system and press so that it s...

Отзывы: