6.5.6.1
Operation on a converter with a low pulse frequency
NOTICE
Increased motor temperature
For operation on a converter with a low pulse frequency, increased losses occur in the motor.
This results in a higher motor temperature.
Reduce the power to prevent exceeding the temperature class and to avoid consequential
premature thermal aging of the insulation.
WARNING
Dangerous voltage via the converter
As long as the feeding converter is switched on, or the DC link of the converter is not
discharged, there can be a voltage at the motor terminals even when the rotor is not moving.
The voltage is up to 1000 V, depending on the converter type.
Ensure that the five safety rules (Page 16) are followed before working on the motor.
6.5.6.2
Converter peak voltage
The values for the maximum converter peak voltage as limit values for the insulation system
are given in the table below:
Table 6-7
Maximum converter peak voltage
Rated converter voltage [V]
Maximum converter peak voltage Û
max
Phase-to-phase
Phase-to-ground
DC link
≤ 500 V
1500 V
Rise time 0.5 μs
1100 V
Rise time 0.5 μs
750 V
> 500 to 690 V
2250 V
Rise time 0.4 μs
1500 V
Rise time 0.4 μs
1125 V
NOTICE
Insulation damage caused by cable reflections
Cable reflections can double the voltage load at the motor or at the terminals. This can
damage the insulation system and result in complete destruction of the machine.
Electrical connection
6.5 Connecting the auxiliary circuits
SIMOTICS TN Series N-compact 1LA8
80
Operating Instructions 05/2014
Содержание 1LA8
Страница 2: ...23 05 2014 10 18 V8 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LA8 12 Operating Instructions 05 2014 ...
Страница 14: ...Introduction 1 1 About these instructions SIMOTICS TN Series N compact 1LA8 14 Operating Instructions 05 2014 ...
Страница 60: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LA8 60 Operating Instructions 05 2014 ...
Страница 88: ...Start up 7 7 De energizing SIMOTICS TN Series N compact 1LA8 88 Operating Instructions 05 2014 ...
Страница 100: ...Operation 8 11 faults SIMOTICS TN Series N compact 1LA8 100 Operating Instructions 05 2014 ...
Страница 173: ...AC Declaration of conformity 1LA8 area 22 AA KE NSR _1LA8_1PQ8_1PP8_1LP8 ...