For a winding temperature of approx. 25° C, the minimum insulation resistances are 20 MΩ
(U ≤ 1000 V) or 300 MΩ (U > 1000 V). The values apply for the complete winding to ground.
Twice the minimum values apply to the measurement of individual assemblies.
Note the following:
● When measuring with winding temperatures other than 40 °C, convert the measuring value
to the reference temperature of 40 °C according to the following equations from IEEE
43-2000.
(1)
R
C
= K
T
· R
T
R
C
Insulation resistance converted to 40 °C reference temperature
k
T
Temperature coefficient according to equation (2)
R
T
Measured insulation resistance for measuring/winding temperature T
in °C
(2)
K
T
= (0.5)
(40-T)/10
40
Reference temperature in °C
10
Halving / doubling of the insulation resistance with 10 K
T
Measuring/winding temperature in °C
In this case, doubling or halving the insulation resistance at a temperature change of 10 K
is used as the basis.
– The insulation resistance halves every time the temperature rises by 10 K.
– The resistance doubles every time the temperature falls by 10 K.
● Dry, new windings have an insulation resistance of between 100 and 2000 MΩ, or possibly
even higher values. An insulation resistance value close to the minimum value could be
due to moisture and/or dirt accumulation. However, the size of the winding, the rated voltage
and other characteristics affect the insulation resistance and may need to be taken into
account when determining measures.
● Over its operating lifetime, the motor winding insulation resistance can drop due to ambient
and operational influences. Depending on the rated voltage, the critical insulation resistance
value is to be calculated by multiplying the rated voltage (kV) by the specific critical
resistance value and then converted to the current winding temperature at the time of the
measurement, see previous table.
Measuring the polarization index
1. To determine the polarization index, measure the insulation resistances after one minute
and ten minutes.
2. Express the measured values as a ratio:
PI = R
insul 10 min
/ R
insul 1 min
Modern measuring devices display these values automatically following the measurement.
For insulation resistances > 5000 MΩ, the measurement of the PI is no longer meaningful and
consequently not included in the assessment.
R
(10 min)
/ R
(1 min)
Assessment
≥ 2
Insulation in good condition
< 2
Dependent on the complete diagnosis of the insulation
Assembly
5.1 Preparations for installation
SIMOTICS TN Series N-compact 1LA8
46
Operating Instructions 05/2014
Содержание 1LA8
Страница 2: ...23 05 2014 10 18 V8 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LA8 12 Operating Instructions 05 2014 ...
Страница 14: ...Introduction 1 1 About these instructions SIMOTICS TN Series N compact 1LA8 14 Operating Instructions 05 2014 ...
Страница 60: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LA8 60 Operating Instructions 05 2014 ...
Страница 88: ...Start up 7 7 De energizing SIMOTICS TN Series N compact 1LA8 88 Operating Instructions 05 2014 ...
Страница 100: ...Operation 8 11 faults SIMOTICS TN Series N compact 1LA8 100 Operating Instructions 05 2014 ...
Страница 173: ...AC Declaration of conformity 1LA8 area 22 AA KE NSR _1LA8_1PQ8_1PP8_1LP8 ...