Connection system
6.1 Power connection
1FT7 Synchronous Motors
224
Configuration Manual, (PFT7S) 01/2009, 6SN1197-0AD13-0BP2
Current-carrying capacity for power and signal cables
The current-carrying capacity of PVC/PUR-insulated copper cables is specified for routing
types B1, B2 and C under continuous operating conditions in the table with reference to an
ambient air temperature of 40 °C. For other ambient temperatures, the values must be
corrected by the factors from the "Derating factors" table.
Table 6- 1
Cable cross section and current-carrying capacity
Cross section
Current-carrying capacity rms; AC 50/60 Hz or DC for routing type
[mm
2
]
B1 [A]
B2 [A]
C [A]
Electronics (according to EN 60204-1)
0,20
-
4,3
4,4
0,50
-
7,5
7,5
0,75
-
9
9,5
Power (according to EN 60204-1)
0,75
8,6
8,5
9,8
1,00
10,3
10,1
11,7
1,50
13,5
13,1
15,2
2,50
18,3
17,4
21
4
24
23
28
6
31
30
36
10
44
40
50
16
59
54
66
25
77
70
84
35
96
86
104
50
117
103
125
70
149
130
160
95
180
165
194
120
208
179
225
Power (according to IEC 60364-5-52)
150
-
-
344
185
-
-
392
> 185
Values must be taken from the standard
Table 6- 2
Derating factors for power and signal cables
Ambient air temperature [°C]
Derating factor according to EN 60204-1 Table D1
30
1,15
35
1,08
40
1,00
45
0,91
50
0,82
55
0,71
60
0,58
Содержание 1FT7 Series
Страница 2: ......
Страница 12: ...Preface 1FT7 Synchronous Motors 12 Configuration Manual PFT7S 01 2009 6SN1197 0AD13 0BP2 ...
Страница 220: ...Motor components 5 4 Gearbox 1FT7 Synchronous Motors 220 Configuration Manual PFT7S 01 2009 6SN1197 0AD13 0BP2 ...
Страница 248: ...Appendix A 3 Suggestions corrections 1FT7 Synchronous Motors 248 Configuration Manual PFT7S 01 2009 6SN1197 0AD13 0BP2 ...
Страница 251: ......