IV394E Rev. 00
Installation and user manual
Date of issue:
2015-12-11
Pag. 30 di 34 + FR
Appendix 3. Specification
Power rating
6kVA/5.4kW 10kVA/9kW
in
p
u
t
Input
Single phase + Ground
Power factor
≥
0.99
rating voltage
220Vac/230Vac/240Vac
δ
can be set
ε
rating frequency
50Hz/60Hz
δ
auto sensing
ε
Voltage range
120~276Vac
Frequency range
45~55Hz/54~66Hz
Bypass voltage range
220Vac max
φ
10%
θ
15%
θ
20% or 25%
θ
default
φ
25%
230Vac max
φ
10%
θ
15% or 20%
θ
d20%
240Vac max
φ
+10% or 15%
θ
d15%
min
φ
20%, 30% or 45%, default 45%
Bypass frequency range ±1%
Ƚ
±2%
Ƚ
±4%
Ƚ
±5%
Ƚ
±10%
THDI
ŏ
3%
δ
100% linear load
θ
input THDV
≤
1%
ε
ŏ
5%
δ
100% non liner load
θ
input THDV
≤
1%
ε
b
a
tte
ry
Battery number
16/18/20pcs
δ
can be set
ε
Battery type
VRLA
Charge model
Boost charge or float charge auto switch
Charge time
Boost charge up to 20Hr(Max)
Charge current(A)
6KVA:1-6 A
10KVA: 1-6 A
o
u
tp
u
t
Output
Single phase + Ground
Output precision
1.0%
χ
Voltage distortion
δ
THD
ε
ŏ
2% at 100% liner load
ŏ
5% at 100% non-liner load
Rating voltage
220/230V /240V
Frequency precision
±0.1%
Rating Frequency
50Hz/60Hz
Frequency track speed
1Hz/s
Overload
105%~110%
θ
1Hr
110%~125% 10min
125%~150% 1min
≥
150% 200ms
Overload for bypass
125%
Peak value factor
3:1
Efficiency at normal
≥
90%
Содержание Green Point
Страница 2: ......