3

EWPX 193(/E) 11/97 ing

Temperature set for the defrost termination
of the second evaporator.

dEA

: dEvice Address.

Allows the selection of the device address
in the remote control network.

FAA

: FAmily Address.

Allows the selection of the device family in
the remote control network.

ndt

: number of digits.

Type of display.
Int = reading without decimal point;
dEc = reading with decimal point, resolu-
tion 0,1 °C;
hFn = reading with decimal point, resolu-

tion 0.5 °C.

Loc

: keyboard Lock.

Allows to disable the keyboard to prevent
unauthorised operations. When the key-
board is disabled only display (not modifi-
cation) of Setpoint and parameters is
allowed. Only the “Loc” parameter can be
modified to permit keyboard unlock.
y = yes; n = no.

PAS

: PASsword.

Allows to set a password (see paragraph
“Password to access parameter program-
ming”).
0 = no password required to access para-

meter programming;
1…15 = available values for the password.

rEL

: rELease firmware.

Read-only parameter showing the release
code of the product.

tAb

: tAble of parameters.

Summary of factory set parameters; can-
not be modified by the user.

MECHANICAL MOUNT

The instrument is designed for panel
mount. Drill a 29x71 mm hole and intro-
duce the instrument, then fix it with the
special bracket (included).
The operating temperature range for cor-
rect operation is from –5 to 65 °C. Do not
install the instrument in moist and/or dirty
places; it is suitable for operation in envi-
ronments with an ordinary pollution level.
Leave enough room for air circulation by
the cooling holes of the instrument.

ELECTRICAL CONNECTIONS

EWPX 193(/E) is provided with four relay
outputs, one serial output for the connec-
tion to the TELEVIS system and another
serial output for the EWPX ECHO repeater
(version /E only).
The instrument includes a screw terminal
block for the connection of electrical ca-
bles with a maximum 2.5 mm

2

section

(one wire only for each block, according to
VDE regulations).
Relay outputs, connected through two
common terminal blocks, are free from
voltage. Do not exceed the maximum al-
lowed current (defrost system second
evaporator and compressor: 8(3)A 250V
AC; defrost system first evaporator and
fans: 5(2)A 250V AC). In case of heavier
loads use a suitable power contactor.
Check the power voltage complies with
the instrument requirements: 12 Vca/cc
±15% (very low safety voltage).
The NTC probe has no insertion polarity
and can be lengthened using a common
bipolar cable (bearing in mind that a very
long probe implies worse instrument per-
formances referred to the EMC). 
Outputs for the connection of the EWPX
ECHO repeater (version /E only) and the
EWRS 485 interface module of the TELE-
VIS system require connections according
to the indicated polarity. 
The probe cable, the connection cable for
the EWPX ECHO repeater (version /E only),
the connection cable for the EWRS 485 in-
terface module shall be kept far from the
relay cables both for EMC and safety rea-
sons. The coordinated European safety
regulations state that the relay contacts
(and generally speaking, all parts subject
to dangerous voltage) shall be kept away
from the very low safety voltage connec-
tions (probe, Televis serial, power supply)
using insulation systems and distances
providing at least a double or reinforced in-
sulation.
However EMC requirements for correct
operation suggest/impose better accuracy

DEFAULT SETTINGS - STANDARD MODELS

Parameter

diF

LSE

HSE

dty

dit

dct

doh

dEt

dSt

FSt

Fdt

dt

dPo

ddL

dFd

APS

Att

HAL

LAL

AFd

PAO

dAo

tAo

Fco

cPP

Ont

OFt

ctP

cdP

odo

PrP

CAL

AAS

dEA

FAA

ndt

Loc

PAS

rEL

tAb

Description

diFferential

Lower SEt

Higher SEt

defrost type

defrost interval time

defrost counting type

defrost offset hour

defrost Endurance time

defrost Stop temperature

Fan Stop temperature

Fan delay time

drainage time

defrost (at) Power-on

defrost display Lock

defrost Fan disable

Alarm Probe Selection

Alarm temperature type

High ALarm

Low ALarm

Alarm (Fan) differential

Power-on Alarm Override

defrost Alarm override

temperat. Alarm override

Fan compressor off

compressor Probe Prot.

On time (compressor)

OFF time (compressor)

compr. type Protection

compr. delay Protection

output delay (at) on

Presence Probe

CALibration

Auxiliary Alarm Setpoint

dEvice Address

FAmily Address

number display type

(keyboard) Lock

PASsword

rELease firmware

tAble of parameters

Range

–12…12

–999…HSE

LSE…999

EL / in

0…31

dF / rt / SC / Fr

0…59

1…250

–999…999

–999…999

0…250

0…250

n / y

n / y / Lb / Lg

n / y

rP / tP

Ab / re

–999…999

–999…999

1…50

0…10

0…999

0…250

oF / on

oF / on / dc

0…250

0…250

nP/don/doF/dbi

0…15

0…99

nP / EP / AP / EAP

–12…12

–999…999

0…14

0…14

int / dEc / hFn

n / y

0…15

/

/

Unit

°C / °F

°C / °F

°C / °F

flag

hours

flag

minutes

minutes

°C / °F

°C / °F

minutes

minutes

flag

flag

flag

flag

flag

°C / °F

°C / °F

°C / °F

hours

minutes

minutes

flag

flag

minutes

minutes

flag

minutes

minutes

flag

°C / °F

°C / °F

number

number

flag

flag

number

/

/

Default

2

–50

40

EL

6

dF

0

30

8

2

0

0

n

n

y

tP

re

50

–50

2

2

60

0

on

on

10

10

doF

0

0

EAP

0

8

0

0

int

n

0

/

/