6.1.2
ID-switch for Module Detection
This group of selection switches has
no function at present.
6.1.3
Operating Mode Selection Switch
Via the operating mode selection switch MODE
at the bottom of the device you can either acti‐
vate the desired configuration or start the
normal operation. The selection switch is evalu‐
ated on startup of the gateway.
Switch position
Operating mode
0
Normal operation
1
No function
2
No function
3
No function
4
No function
5
No function
6
No function
7
No function
8
No function
9
Configuration: Speed zero with OSSD signals
6.1.4
Drive Selection Switches
Via the DIP switches at the bottom side of the
gateway you select the drives for speed zero
monitoring.Due to the PROFIBUS module you
can select max. 12 drives. The maximum
number of drives depends on the data length of
the input data (14 or 16 bytes).
Each DIP switch is assigned to a connected
drive and can have the following states:
Switch position
Meaning
Off
Drive operates without speed zero monitoring
On
Drive operates with speed zero monitoring
Connectors, Switches and Displays
W
30
Gateway 0362151A - PROFIBUS to SERVOLINK 4 Safety
6
Содержание 036215
Страница 1: ...Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety P TD 0000331 12 2019 04 09 SIEB MEYER W ...
Страница 4: ...Chapter Overview W 4 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety ...
Страница 16: ...Safety Instructions W 16 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 2 ...
Страница 18: ...Unit Assembly Complying EMC W 18 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 3 ...
Страница 26: ...Gateway 0362151A W 26 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 4 ...
Страница 28: ...Mounting and Demounting W 28 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 5 ...