CONNECTING THE REFRIGERANT LINES TO THE WATER TANK

Step 1.

 Carefully unwind the copper refrigeration pipes on the heat pump, take care to avoid kinking the pipes. The pipes are 

quite hard copper and will kink if care is not taken to carefully mould or form the curve required.  If a tight bend to the right is 
required in the refrigeration lines, cut back the insulation and use a soft copper tube bender to form the bend. The insulation 
must be taped back in place once the bend is made.

Step 2. 

Remove the lower cover on the tank, find the two male refrigeration pipe 

couplers; you may need to gently pull them out from the tank if you find them 
difficult to access.

Step 3. 

Important!

 Feed the couplers and refrigerant lines through the holes in 

the cover plate to align with the respective couplers on the tank. 

You cannot undo the couplers later if you forget this step.

Step 4.  

Carefully align the male & female couplers before tightening, misalignment 

can cause rupture or displacement of the internal “O-Ring” seal, causing refrigerant 
leakage & defective performance. 

Use some mineral oil on the threads and rubber O-Ring and ensure the coupling nuts 
are fully tightened using two spanners, one on each half of the coupling then draw 
the coupling halves together tightly; please note you will feel some resistance when 
the  metal  diaphragms  are  punctured  to  facilitate  refrigerant  flow;  keep  tightening 
until you feel the “O-Ring” seal fully seated otherwise gas will leak under the high 
operating pressures.

Note:

 There should be little or no thread showing on the connectors when the couplers 

are fully tightened.

Step 5. 

Refit the lower cover plate and tighten the 4 Stainless Steel screws.

CONNECTING THE HEAT PUMP UNIT

Step 1. 

Remove the side cover “A” by removing screw “B”.

Pull the cover out slightly at the bottom and push the cover 
downwards a few millimetres to release tabs.

Step 2. 

Check that the flare fittings 

(Note A)

 on the line 

connectors are still very tight to ensure no gas leakage here. (If they 
are loose, the line may have leaked gas and could need service.)

Step 3. 

Remove the cover caps on the refrigerant gas valves.

Step 4. 

Open the two refrigerant gas flow valves at the base of the heat pump using a 5mm 

hex key. Turn the large valve approx 6 turns anti clockwise, & the smaller valve approx 2.5 
turns anti-clockwise. 

Note:

  We recommend using soapy water on the couplers and flare 

fittings to check gas leaks. 

(Note A)

Step 5. 

Replace the cover caps on the refrigerant valves and refit the plastic side cover to 

the Heat Pump unit

.

SECTION 3: HEAT PUMP  TO TANK CONNECTIONS

Side Cover “A”

Screw “B”

Note (A) Check flare fittings 
are tight before opening 
valves

Open the refrigerant gas valves only 
once you have checked the connections 
are all made correctly and are tight

4

Содержание 264SSBD

Страница 1: ...lly before undertaking the installation of a Siddons Solarstream Heat Pump Water Heater INSTALLATION AND USER MANUAL INSTALLERS Models Domestic 264SSBD 327SSAD Commercial 327SSAC3 AC4 AC5 AC6 www sidd...

Страница 2: ...ection for the Solarstream Heat Pump Water Heater if shelter is available such as an overhanging eave it is a good idea to use it The Heat Pump unit is designed to be installed outside In cold conditi...

Страница 3: ...and Pressure and Temperature P T relief valve Ensure the specification label is visible Installation must comply with Australian Standard AS NZS 3500 4 and any local authority regulations OUTDOOR For...

Страница 4: ...NCE APART The maximum length of refrigerant line to be connected to the Heat Pump is 9 metres E g 2 metre standard 7 metre extension total 9 metres max Drwg A REFRIGERANT LINES IN DUCTS WALLS OR SURFA...

Страница 5: ...ill feel some resistance when the metal diaphragms are punctured to facilitate refrigerant flow keep tightening until you feel the O Ring seal fully seated otherwise gas will leak under the high opera...

Страница 6: ...230 240 volt ac power It is a 1 5 mm2 cable protected in UV resistant flexible conduit Fit the wiring loom through the cable hole in top inspection cover on the Water Tank and secure with the conduit...

Страница 7: ...ump unit Check the Heat Pump continues to run for at least 20 minutes on first start up Warm water should be evident at hot taps in about 60 minutes Check firstly that the Heat Pump is connected to an...

Страница 8: ...ndicated period from the date of the original purchase Should a part of the complete Water Tank component be replaced during this period only the balance of the original warranty will continue to rema...

Отзывы: