7.8
Interfaces
workflow step
7.8.1
Configuring the digital in- and outputs
The digital I/O interfaces are available on the Power I/O connector, see
. I/O 4, 5, 6 and 7 are configurable and can be used for either input or
output signals.
Configure I/O as input
1.
Set the
Type
parameter in the
I/O Definitions
table to
In
.
2.
Set the input signal level (
Active
parameter) to
High
(24 V) or
Low
(0 V).
3.
Set the minimum input signal length by the
Debounce
parameter (1 ms is default).
Configure I/O as output
1.
Set the
Type
parameter in the
I/O Definitions
table to
Out
.
2.
Set the output signal level (
Active
parameter) to
High
(24 V) or
Low
(0 V).
Once an I/O has been configured as output, its output signal can be set in the
Digital
outputs
section in the
Results
workflow step.
7.8.2
Using the command channel
A command channel is a camera interface which is used for external modification
of image and tool parameter settings. The following command channel interfaces are
available for the TriSpector1000:
■
Ethernet (TCP/IP).
■
Serial.
■
EtherNet/IP, see
"Setting up a TriSpector1000 to communicate via EtherNet/IP",
.
"Available commands for command channel", page 67
for a full list of available
commands.
To use TCP/IP as command channel interface:
1.
Select the
Command channel
checkbox in the
Ethernet
section in the parameter pane.
2.
In the
Server/client
drop-down menu, select to act as server or client (depending on
the settings of the connected device).
3.
Set port number in the
TCP Port
text field. 2115 is the default port.
To use the serial interface as command channel interface:
1.
Select the
Command channel
checkbox in the
Serial
section in the parameter pane.
7.8.3
Sending an output string
The following interfaces are available for sending an output string from the TriSpec‐
tor1000 to a connected device:
■
Ethernet (TCP/IP).
■
Serial.
■
Ethernet/IP, see
"Setting up a TriSpector1000 to communicate via EtherNet/IP",
.
7
OPERATION
50
O P E R A T I N G I N S T R U C T I O N S | TriSpector1000
8021808/12ID/2019-01 | SICK