5.
When the ERR display starts to flash, release the Enter pushbutton again within
3 seconds.
✓
The selected operating mode is stored as a non-volatile setting and is active.
NOTE
If the Enter pushbutton is pressed for longer than 3 seconds, the entire system will
change to error status. The ERR display flashes.
All subsequent changes to the wiring at S1, S2 or S3 will lead to lock-out (ERR).
7.2.2
Configuring the safety laser scanner
NOTE
A protective field must be configured in the safety laser scanner which acts on the
OSSDs connected to the Flexi Classic safety controller.
7.2.2.1
Configuring the S300 Mini Standard
The S300 Mini Standard is configured with the CDS (Configuration & Diagnostic Soft‐
ware).
For configuration, refer to the S300 Mini Standard operating instructions.
NOTE
The resolution must be set in accordance with the risk assessment and the height of
the scan plane. For recommended values,
see "Mounting the safety laser scanner",
.
NOTE
The height of the scan plane must be checked,
see "Mounting the safety laser scan‐
.
Configuring the protective field
Figure 16: S300 Mini Standard configuration view (example)
7
CONFIGURATION
42
O P E R A T I N G I N S T R U C T I O N S | sBot Stop
8023421/12KF/2019-01-22 | SICK