
Operating
Instructions
PBS
plus
O P E R AT I N G I N S T R U C T I O N S P B S p l u s
8024946 | SICK AG
Subject to change without notice
5 6
6. FAULTS
Warning
Description
ATT5
Maximum turn down exceeded
ILOC
Menu locked by IO-Link
OL
Overload pressure, measuring range exceeded > about 3.125% (digital display flashes)
PAS
Request for password entry
UL
Underload pressure, measuring range undercut < about 3.125% (digital display flashes)
Error
Description
ERR
Internal error (device restart or reset to factory setting could help)
The analog output controls the alarm signal ≤ 3.6 mA (4 ... 20 mA output signal) or
≥ 11 V (0 ... 10 V output signal) in accordance with NAMUR43
The switching outputs maintain the current switching state (output open or closed)
ERR1
Device temperature exceeded/undercut or auxiliary energy undercut
The analog output is output. There are limits regarding accuracy (influence of tempera
-
ture) and maximum analog value (auxiliary energy undercut)
The switching outputs maintain the current switching state (output open or closed)
ERR2
Sensor defect detected, check whether high overload pressure exists (can be detected
as sensor defect), a device restart or device exchange may be necessary
The analog output controls the alarm signal ≤ 3.6 mA (4 ... 20 mA output signal) or
≥ 11 V (0 ... 10 V output signal) in accordance with NAMUR43
The switching outputs maintain the current switching state (output open or closed)
SC
Short-circuit on switching output 1 or 2 detected
The affected switching output is deactivated as long as the short-circuit exists
Confirm warnings and errors with confirmation pushbutton.
Содержание PBS plus
Страница 131: ......