Electrical installation
5.4.3
Non-SICK Power supply unit/connections without the Connection Module
Power output
If a non-SICK Power supply unit is used instead of the AMS60, it must be capable of
providing the following voltage and power values:
•
for CLX without heater: 18 to 30 V DC, min. 20 W continuous power output
•
for CLX with heater: 24 V DC +20 %/–10 %, min. 100 W
The non-Sick Power supply unit must provide the functional extra-low voltage in accordance
with IEC 364-4-41.
The output circuit must be reliably electrically isolated from the input circuit. To do so,
use a safety isolating transformer pursuant to IEC 742.
Wire cross-section
The wire cross-section for the power supply (Pin 1/Pin 5) should be at least 0.15 mm
2
, or
0.75 mm
2
for CLX with heater, with a max. length of 10 m.
a) Connecting the CLX without a connector cover/external parameter memory
The two cables no. 2020303 and no. 2020264 with open cable end on one side are re-
quired to connect the CLX. The wire color assignments are shown in
and
.
The cables must not be extended for CLX with heater.
Connection cable no. 2020203 ("Host/Term" connection)
15-pin D Sub HD socket and open cable end.
Pin Signal
Wire
color
1
1)
V
S
Red
2
RxD (RS 232), Auxiliary
White
3
TxD (RS 232), Auxiliary
Brown
4
Term (RS 422/485)
Violet
5 GND
Blue
6
RD+ (RS 422/485), Host
Green
7
RD– (RS 422/485), Host
RxD (RS 232), Host
Yellow
8
TD+ (RS 422/485), Host
Grey
9
TD– (RS 422/485), Host
TxD (RS 232), Host
Pink
10 CAN
H
Grey-pink
11 Reserved
Red-blue
12 CAN2
H
White-green
13 CAN2
L
Brown-green
14 Reserved
White-yellow
15 CAN
L
Yellow-brown
–
Shield Orange
1) Pin 1 is jumpered with Pin 1 of the "I/O" connection in the CLX
Table 5-10: Wire color assignment of the cable no. 2020303