O P E R AT I N G I N S T R U C T I O N S | L F P I N OX
8019921/15H0 / 2019-09-30| S I C K A G
Irrtümer und Änderungen vorbehalten
4 5
10
OVERVIEW OF PARAMETERS
10
Overview of parameters
Parameter
Description
Q1MENU, Q2MENU,
Q3MENU, Q4MENU
“8.2 Configuring the switching outputs”.
SPx
Switching point, switching output 1 or 2 or 3 or 4
(SPx > RPx).
Note: Not displayed if the switching output in the OUx
menu is set to error or window.
RPx
Reset switching point, switching output 1 or 2 or 3 or 4.
Note: Not displayed if the switching output in the OU2/3/4
menu is set to error or window.
FHx
FLx
• Upper threshold (high) window function, switching out-
put 2/3/4 (FHx > FLx)
• Lower threshold (low) window function, switching output
2/3/4
Note: Not displayed if the switching output in the OU2/3/4
menu is set to error or hysteresis.
OUx
Switching function, switching output.
•
Qx-Hno = Hysteresis function, normally open
•
Qx-Hnc = Hysteresis function, normally closed
• Qx-Fno = Window function, normally open (function only
available for Q2/3/4)
• Qx-Fnc = Window function, normally closed (function
only available for Q2/3/4)
• Qx-Eno = Error signal, normally open (function only avail-
able for Q2/3/4)
• Qx-Enc = Error signal, normally closed (function only
available for Q2/3/4)
If Qx is used as an error signal, SPx/FHx and RPx/FLx are
hidden in the menu.
SimQx
“8.4.6 Testing the configuration”.
TYP2/3/4
• Qx-PNP = Switching output in PNP circuit
• Qx-NPN = Switching output in NPN circuit
• Qx-Drv = Switching output executed in push/pull func-
tion
QAMENU
“8.3 Configuring the analog output”.
QAHIGH
Input of the fill level in mm for 20 mA / 10 V signal
(QAHIGH > QALOW).
QALOW
Input of the fill level in mm for 4 mA / 0 V signal.
QAPOL
The analog output signal can be inverted.
•
QA-Nrm = Analog output signal as configured
• QA-INV = Analog output signal is inverted: QA
H
igh
4 mA / 0 V and QALow 20 mA / 10 V