THR
PRO
TCH
PWR
Q
Automated (sender color selected during teach-in)
THR
PRO
TCH
PWR
Q
Sender color red
THR
PRO
TCH
PWR
Q
Sender color green
THR
PRO
TCH
PWR
Q
Sender color blue
7.
Press the SET pushbutton.
7.8.9
Setting contamination tracking
In difficult application conditions (e.g., due to dust deposits or varying print quality),
contamination tracking can be used to optimize the stability of detection. This is acti‐
vated at the factory.
NOTE
If the switching threshold has been manually adjusted, the AdC function is deactivated.
NOTE
With the high precision variant, the function is deactivated at the factory.
1.
Press the SET pushbutton.
2.
Use the plus or minus pushbutton to select Pro.
THR
PRO
TCH
PWR
Q
3.
Press the SET pushbutton.
4.
Use the plus or minus pushbutton to select AdC.
THR
PRO
TCH
PWR
Q
5.
Press the SET pushbutton.
6.
Use the plus or minus pushbutton to choose between activated and deactivated
contamination tracking.
THR
PRO
TCH
PWR
Q
Contamination tracking active
THR
PRO
TCH
PWR
Q
Contamination tracking deactivated
7.
Press the SET pushbutton.
7.8.10
Rotating the display
If the installation position of the device makes it difficult to read from the segment dis‐
play, the display can be rotated 180°.
1.
Press the SET pushbutton.
2.
Use the plus or minus pushbutton to select Pro.
OPERATION
7
8020708.ZMT3/ | SICK
O P E R A T I N G I N S T R U C T I O N S | KTS/KTX Prime
39