IO-Link 5-pin
Male connector
Pin Signal
Meaning
Color
1)
1
VDC
24 V IO-Link supply voltage
2)
Brown
2
AUX_IN
Non-safe input
White
3
GND
GND supply voltage
Blue
4
C/Q or
AUX_OUT
IO-Link interface/non-safe output
Black
5
NC
Not connected
Gray
Table 20: Pin assignment for IO-Link or AUX_IN / AUX_OUT 5-pin (male connector)
1)
The stated colors apply on the usage of pre-assembled cables (should be checked).
2)
IO-Link and Flexi Loop must have separate supply voltages.
6.2.10
Connections of the DIAG Flexi Loop accessory
Figure 52: Connections of the DIAG Flexi Loop accessory
1
FL_IN (male connector)
2
FL_OUT (female connector)
FL_IN 5-pin
Male connector
Pin Signal
Meaning
Color
1)
1
VDC
24 V supply voltage
Brown
2
DATA_OUT
Output to the Flexi Soft input In
+ 1
White
3
GND
GND supply voltage
Blue
4
SAFE_OUT
Safe shutdown signal
Output to the Flexi Soft input In
Black
5
DATA_IN
Input from the Flexi Soft output Xn Gray
Table 21: Pin assignment FL_IN (male connector)
1)
The stated colors apply on the usage of pre-assembled cables (should be checked).
6.2.11
Connection of Flexi Loop YCON1 and YCON2 adapters
The Flexi Loop YCON1 and YCON2 adapters are used to decouple the non-safe inputs
and outputs of the Flexi Loop EMSS8 or OSSD8 nodes.
6
ELECTRICAL INSTALLATION
50
O P E R A T I N G I N S T R U C T I O N S | Flexi Loop
8015836/YT10/2016-05-24 | SICK
Subject to change without notice