12
Technical data
12.1
Data sheet
Safety-related parameters
Table 12: Safety-related characteristic data - safety capable inputs (I)
Safety capable inputs (I)
Single-channel
Dual channel
Without test
pulses
1)
With test pulses
Without test
pulses
2)
With test pulses
Safety integrity
level (IEC 61508)
SIL 2
SIL 3
SIL 3
SIL 3
SIL claim limit
(IEC 62061)
SILCL 2
SILCL 3
SILCL 3
SILCL 3
Cate‐
gory (ISO 13849-
1)
Category 3
Category 4
Category 4
Category 4
Performance
level (ISO
13849-1)
PL d
PL e
PL e
PL e
PFH
D
(h
-1
)
1 × 10
-9
1 × 10
-9
0.5 × 10
-9
0.5 × 10
-9
PFD
avg
4 × 10
-5
4 × 10
-5
4 × 10
-5
4 × 10
-5
MTTF
D
ISO
13849-1
[years]
500
500
500
500
T
M
ISO 13849-1
[years]
20
20
20
20
1)
If you are using single-channel safety inputs (I) without test pulses for a safety-related application, then
a protected or separate cabling is required for these safety inputs in order to achieve the safety-related
characteristics. Reason: Short-circuits to the supply voltage or cross-circuits are not detected.
2)
If you are using dual-channel safety capable inputs (I) without test pulses, the safety function must be
requested at least once a year.
Table 13: Safety-related characteristic data - CPU logic processing
CPU logic processing
Safety integrity level (IEC 61508)
SIL 3
SIL claim limit (IEC 62061)
SILCL 3
Category (ISO 13849-1)
Category 4
Performance level (ISO 13849-1)
PL e
PFH
D
(h
-1
)
3 × 10
-9
PFD
avg
20 × 10
-5
MTTF
D
ISO 13849-1
[years]
500
T
M
ISO 13849-1
[years]
20
12
TECHNICAL DATA
32
O P E R A T I N G I N S T R U C T I O N S | Flexi IO XTDO1
8024583/2020-11-10 | SICK