Figure 35: Changing data format
7.
Under
Size
, select the
DINT
data format.
8.
Then click on
OK
.
Checking communication
The data received by the controller from the encoder can be displayed in order to check
that communication between the controller and the encoder is working correctly.
Figure 36: Checking communication
1.
In
Controller Organizer
, open the
Controller test
→
Controller Tags
folder.
2.
In
Controller Tags
, in the
Name
column, open the
AFx60_EIP:I1
→
AFx60_EIP:I1.Data
item.
Displayed data in the example:
•
AFx60_EIP:I1.Data[0]
: Fault header: 0
•
AFx60_EIP:I1.Data[1]
: Position: 1037225780
•
AFx60_EIP:I1.Data[2]
: Speed: 252
5.4.3
Configuration
Figure 37: Encoder configuration
1.
In
Controller Tags
, in the
Name
column, open the
AFx60_EIP:C
item.
2.
Enter the parameters of the encoder (
see "Parameterizable functions", page 36
CONFIGURATION USING A PLC
5
8014213/1EF3/2021-12-08 | SICK
O P E R A T I N G I N S T R U C T I O N S | AFS/AFM60 EtherNet/IP