From Dx1000
<STX>sAN rs422PeriodicOutputContent<ETX>
To Dx1000
<STX>sMN mEEwriteall<ETX>
From Dx1000
<STX>sAN mEEwriteall 1<ETX>
To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
then continuously from
Dx1000 Example:
5,378 mm, CRLF mode
+0005378<CR><LF>
…
Switching off continuous, permanent distance value output
Table 19: Example: Switching off continuous, permanent distance value output
To Dx1000
<STX>sMN SetAccessMode 4 81BE23AA<ETX>
From Dx1000
<STX>sAN SetAccessMode 1<ETX>
Continuous output of
Dx1000 stops
To Dx1000
<STX>sWN rs422PeriodicOutputContent 0<ETX>
From Dx1000
<STX>sAN rs422PeriodicOutputContent<ETX>
To Dx1000
<STX>sMN mEEwriteall<ETX>
From Dx1000
<STX>sAN mEEwriteall 1<ETX>
To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
Setting preset value to 10 m
Table 20: Example: Setting preset value to 10 m
Designation
Syntax
To Dx1000
<STX>sMN SetAccessMode 4 81BE23AA<ETX>
From Dx1000
<STX>sAN SetAccessMode 1<ETX>
To Dx1000
<STX>sWN preset 2710<ETX>
From Dx1000
<STX>sWA preset<ETX>
To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
Executing preset
Table 21: Example: Executing preset
Designation
Syntax
To Dx1000
<STX>sMN SetAccessMode 4 81BE23AA<ETX>
From Dx1000
<STX>sAN SetAccessMode 1<ETX>
To Dx1000
<STX>sMN activatePreset<ETX>
From Dx1000
<STX>sAN activatePreset<ETX>
To Dx1000
<STX>sMN Run<ETX>
From Dx1000
<STX>sAN Run 1<ETX>
3.7.4
PROFIBUS DP interface
3.7.4.1
Basics
All PROFIBUS users are connected in a bus structure (line), which can consist of several
segments. Up to 32 users can be interconnected as masters or slaves in one segment.
3
PRODUCT DESCRIPTION
26
O P E R A T I N G I N S T R U C T I O N S | DT1000 PROFIBUS DP and DL1000 PROFIBUS DP
8024560/1A19/2021-06-30 | SICK