3.7
AFS/AFM60 PROFINET, device handling in the network
Dear valued customer,
please download the operating instructions and the GSDML file for the AFS/AFM60
PROFINET from our homepage
. For this, please enter the seven-digit
part number of your encoder directly in the field “Search” on the welcome page. Then
please click on the searching result and you will be forwarded to all information and
files for your product.
The following encoder feature can be configured via the hardware:
•
Preset function
The following measures are necessary in order to run one of these functions
•
Remove screw-on cap from the back of the encoder
GND
2
3
1
4
10–30 V DC
WARNING
DO NOT
USE
x10
x100
x1
SF
BF
L/A1
L/A2
Port
P
1
ort 2
Encoder
a
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
DEC Switches out of operation
Preset
push-button
3.7.1
Preset button hardware (see technical information 8015078 for software)
The encoder is set to a special pre-defined value when the PRESET function is activated
by pressing the Preset button. The works default value is zero (0).
•
Remount screw cap.
Screw cap tightening torque: 0.8 Nm
3.7.2
Reset to factory settings and deleting of device name
enum-title
•
Remove screw-on cap from the back of the encoder.
•
Only connect the cable for the supply voltage to the encoder.
•
Set the three address switches to 888.
•
Press the Preset pushbutton for 5 seconds. The encoder LED flashes green.
•
The encoder is reset to the factory settings and the device name is deleted.
•
Remount screw cap.
Screw cap tightening torque: 0.8 Nm
MOUNTING INSTRUCTIONS
8015211/1EF3/2021-12-02 | SICK
M O U N T I N G I N S T R U C T I O N S | AFS/AFM60 PROFINET
15
Subject to change without notice