Group 3: Cables which are a source of interference, such as control cables
for inductive loads, motor brakes
°
Group 4: Cables which are powerful sources of interference, such as output
cables from frequency inverters, welding system power supplies, power
cables
b
Cables in groups 1, 2 and 3, 4 must be crossed at right angles,
.
b
Cables in groups 1, 2 and 3, 4 must be routed in different cable channels or
metallic separators must be used,
. This applies
particularly where cables of devices with a high level of radiated emission,
such as
frequency converters, are laid parallel to sensor cables.
1
2
4
3
1
2
4
3
90
90
Figure 6: Cross cables at right angles
1
2
3
4
Figure 7: Ideal laying – Place cables in different cable channels
1
2
3
4
Figure 8: Alternative laying – Separate cables with metallic separators
NOTE
Prevent equipotential bonding currents via the cable shield with a suitable earthing
method,
6
ELECTRICAL INSTALLATION