22 User manual GC600-GC600
Mains
configured text for the analogue input and relative measure. If more than 9 measures are
associated to one of these pages, the controller shows them all, rotating them on the display every
two seconds.
By keeping the
Esc/SHIFT
button pressed, the rotation on current view can be stopped.
The page
E.14 (SERVICE)
displays the counters related to the Genset maintenance. The page is
hidden, if no time limits are set for maintenance operations.
The pages
E.15-16-17-18 (EXHAUST GAS TREAT.)
display the icons and the measurement related to
the engine emission system, acquired from the engine’s ECU. These icons and measurements
are compliant with TIER 4 / STAGE 5 standard.
The pages
E.19-20-21-22-23-24
are defined by the configuration files of the ECU of the engines. Using
these files, it is possible to create custom pages showing the information got from the ECU that
are not J1939 standard (specific for that ECU).
In this mode are shown the measures and the statuses which are connected and transit on the CAN-
BUS PMCBus, which connects SICES devices among them. All pages of this mode are displayed only
if the CAN-BUS PMCBus is enabled.
The page
B.01 (DEVICES ON PMCB)
displays, for diagnostic purposes, the mains controllers (MC100)
and tie breaker controllers (BTB100) connected to the PMCBus.
The pages
B.02, B.03, B.04 (GENSETS)
display the information related to the
PMC-Bus
mains (PMC-
Bus address, active and reactive power and status) up to 8 gensets.
The status is displayed in red if the genset is not available for the operation in automatic. Inside a
page, each controller shows the generator data, managed by itself, in reverse.
Page
B.05 (TOTALS ON PMCB)
displays the totals calculated on all genset control boards connected
to PMCBus. The total rated power of the gensets (MDPt, kW), the total active power (kW), the total
reactive power (kvar), the total active energy (kWh) and the total reactive energy (kvarh).
The pages
B.06 (LOAD FUNCTION)
display the information related to the load function. This includes
the number of network devices, the operating mode of the load function, the identifier of the pilot
generator and the list of priorities. It is possible to manually select
The pages
B.07 (LOAD FUNCTION)
display the information related to the load function.
The power supplied by the gensets (percentage compared to the maximum that the gensets
currently supplying can afford).
The threshold (%) over which a new genset must start (or you need to pass to the
combination of higher gensets compared to the rated power level).
The power supplied by the gensets (percentage compared to the maximum) calculated in
the hypothesis that the less priority genset is stopped (or that you select a combination of
gensets which is lower for rated power).
The threshold (%) to be compared with the calculated power at the previous point, under
which the less priority genset must be stopped (or you need to pass to the combination of
lower gensets compared to the rated power level).
If, in addition to the normal “load management” also the management of the load reserve is enabled,
this page alternates the above written values every two seconds with:
The current load reserve (the difference between rated power of the gensets and the supplied
power).
The minimum load reserve to activate a new genset.