24
User’s Manual
Disabling
Bit 7 of the Parameter P39 = 0
Conditions for its
activation
No block
Engine running
Shutdown cycle not in progress
Voltage measured at the D+WL input (terminals 39-40) under
the threshold of 8 (or 16) V.
Filter time
20 seconds
Visual signal
Message “F05” on the display “MULTIFUNCTION”
Disabling
Cannot be disabled
Conditions for its
activation
No block
Selector on AUTO or TEST
Engine running
Fuel solenoid activated
The generator doesn’t get in operating window (for two
seconds) within the time limit set through the parameter P32
from the engine start.
Filter time
Immediate
Visual signal
Message “F08” on the display “MULTIFUNCTION”
Disabling
Cannot be disabled
Conditions for its
activation
No block
Selector on AUTO or TEST
Engine not running after P10 starting attempts
Filter time
Immediate
Visual signal
“OVERCRANK” indicator slowly flashing
Disabling
Cannot be disabled.
Conditions for its
activation
No block
Detected hardware fault on generator voltage measurement.
Filter time
Immediate
Visual signal
Message “F50“ on the display “MULTIFUNCTION”