3.3 – Maintenance  

Please mind to check the battery 
efficiency about every 12 months as 
follows: 

• Switch off the timer for about 15 
minutes. 
• Switch on the timer and check the time 
indicated on the display. If the time 
displayed is midnight (00.00), it is 
necessary to replace the battery with 
the spare part code 867.  The following 
servicing operations must always be 
performed when the controller is off 
power. When replacing the sole 
electronic board, and each time you 
must operate with the case opened, 
avoid as much as possible touching 
components and welded parts with your 
hands, especially near the CPU, since 
electrostatic discharges could eventually 
damage the controller. Furthermore, we 
recommend not to place the electronic 
board on a metal surface, unless it is 
properly insulated (a few paper sheets 
will be sufficient). To store electronic 

boards, please always use the anti-static 
e n v e l o p e s   t h a t   c o m e   w i t h   t h e  
replacement kits.  Avoid the electronic 
board to come in contact with liquids. In 
case it happens, please dry it with an air 
spray.   

3.4 – Safety devices  

The controller is provided with the 
following safety devices :  
• Safety and insulation transformer. 
•  Safety electronic circuit against voltage 
peaks and disturbances. 
• Autoreset (par. 4.9) – Available from 
version 9/98

4 – INSTRUCTIONS FOR USE  
4.1 – Powering on  

XP Controller is not provided with power 
switches. Powering on is obtained by 
connecting the power transformer to the 
outlet.   

4.2 – Working  

After powering on, the display located 
on the front panel displays the timer. If 
the battery needs replacement, the time 
will display midnight (00.00), otherwise 
an updated time. When powering on for 

the first time, it is advisable not to switch 
off the controller for at least 24 hours on 
end, in order to avoid an anomalous 
battery charge.  The regeneration starting 
modalities are the following:  Time Start 
at the programmed time after the preset 
interval days have elapsed. Mixed Start 
at the programmed time without waiting 
for the interval days when the treatable 
volume is exhausted. (This modality is 
available in the volumetric version only).

4.3 – Programming

XP Controller is programmed using the 
hidden key, and the values can be 
modified using the Advance key. 
Proceed as follows to program :  

Programming table (Tab. 2)
- 1 HIDDEN KEY =

 0.2 3 0 Regeneration 

starting time. The minutes flash.  

- 2 HIDDEN =

 KEY 0.2 3 0 Regeneration 

starting time. The hours flash. 

- 3 HIDDEN KEY =

 F F 0 7 The interval in 

days between two regeneration 
processes. (from 1 to 14 days) 

- 4 HIDDEN KEY = 

2 0 0.0 The treatable 

volume. The digits on the right-hand side 
flash. 

- 5 HIDDEN KEY = 

2 0 0.0 The treatable 

volume. The digits on the left-hand side 
flash. 

- 6 HIDDEN KEY =

 0 0 0 0. The volume 

reserve. The digits on the right-hand side 
flash. 

- 7 HIDDEN KEY =

 0 0 0 0. The volume 

reserve. The digits on the left-hand side 
flash. 

- 8 HIDDEN KEY = 

A A 1 4 The volume

program the treatable volume. Using the 
SIATA magnetic liter-counter sensor, the 
value of the divider (AA14, step 8 in Tab. 
2) must be set to 14, which means that 

the available volume is reduced by one 
liter every 14 impulses issued by the sensor. 
In this way the maximum treatable 
volume that can be programmed is 
10.000 liters. If you need to use a larger 
volume, it is possible to do a simple 

arithmetical operation, that is to multiply 
by two, by three, by four, etc. the divider 
and at the same time divide by two, by 
three, by four, etc. the treatable volume. 
In the event you wish to program a 
reserve, it is necessary to divide it as well 
as the volume. 
Examples:   
• 15.000 liters of water must be treated, 
to obtain a reserve of 1.000 liters:
- Volume/2 = 15.000/2 = 7500 in steps 4 
and 5 in tab. 2 
- Reserve/2 = 1.000/2 = 500 in steps 6 and 
7 in tab. 2 
- Divider x 2 = AA14 x 2 = AA28 in step 8 
in tab. 2
• When starting operations the treatable 
volume will be 7000 liters (7500 – 500).  
50.000 liters of water must be treated, to 
obtain a reserve of 1.000 liters:
- Volume/5 = 50.000/5 = 0000 in steps 4 
and 5 in tab. 2 

- Reserve/5 = 1.000/5 = 200 in steps 6 and 
7 in tab. 2 
- Divider x 5 = AA14 x 5 = AA70 in step 8 
in tab. 2
When starting operations the treatable 
volume will be 9800 liters (10000 – 200). 
Please note that programming the 
volume by setting the 0000 value, means 
programming 10.000, while setting the 
AA00 value for the divider means 
programming the divider as 100.  You 
can treat maximum 70.000 liters water 
with the SIATA magnetic sensor by 
programming 10.000 liters for the 
treatable volume and AA98 for the 
divider (Volume / 7 and divider x 7).  If 
you use a counter issuing one impulse 
every liter (or cubic meter), the maximum 
treatable volume will be 1.000.000 liters 
(or cubic meters) if you set to 10.000 liters 
the treatable volume and to AA00 the 
divider (corresponding to 100 impulses 
every liter or cubic meter). In case you 
are using high flow rate Reed counters, 
such as 1imp./1m3, the low rotation 
speed of the magnet could cause 

spurious impulses that will be calculated 
as real impulses. 

4.8 – Testing the regeneration automatic 
start  

To test the regeneration automatic start, 
proceed as follows:  
-   C a s e   1 ,   X P   C o n t ro l l e r   i n   t h e  
Chronometrical version.  

• On steps 1 and 2 in tab. 2, set 0000 for 
the regeneration time. 

• On step 3 in tab. 2, set 1 as the number 
of interval days. 

• Quit programming and perform a 
regeneration process. 

• If you are using a 9/98 or later version, 
use the Man. Regen. key to exploit the 
step-by-step functionality. 

• Once the regeneration has terminated, 
set the timer to 23.59 and wait for it to 
indicate midnight. 

• When midnight is displayed on the timer 
the regeneration will start.   

- Case 2, XP Controller in the Volumetric

counter divider. The digit flashes. 

- 9 HIDDEN KEY =

 P r - - Value not currently 

in use, to be ignored. The digit does not 
flash. 

- 10 HIDDEN KEY =

 P r - - The display is still 

indicating the same value.  

- 11 TIME OF D. =

 F r 5 0  Power Frequency 

(50 or 60 Hz.) 

- 12 TIME OF D. =

 1 C 1 0 Stopping time 

for the first regeneration phase. 

- 13 HIDDEN KEY = 

2 C 3 0 Stopping time 

for the second regeneration phase. 

- 14 HIDDEN KEY =

 3 C 2 0 Stopping time 

for the third regeneration phase. 

- 15 HIDDEN KEY =

 4 C 1 0 Stopping time 

for the fourth regeneration phase. 

- 16 HIDDEN KEY

 = E n d - End of 

programming. It quits after 3 seconds.   

- 1 2 3 0 

The display shows the local time 

again.
Pressing the Hidden key instead of the 
Time of Day key at step 11 of tab. 2 will 
quit programming without accessing the 
regenerative cycle phases. The latter is 
the recommended procedure. Attention! 
If the controller  is used in chronometric 
regeneration start and the treatable 
volume value has been set up to 0 (zero), 
every day a regeneration cycle will be 
performed.  

IMPORTANT !! Changes per formed 
according to the tab. 2 steps becomes 
operational after the first regeneration 
only. Modifying the programming without 
immediately performing a regeneration 
process will result in a behavior compliant 
with the previous programming, not with 
the new one.

The local time is set using the Time of Day 

key and the values can be modified using 
the Advance key. Proceed as follows to 
perform programming:  

Local time setting (Tab. 3)
- 1 TIME OF DAY = 

0 8 0 0 Local time. The 

minutes flash.  

- 2 TIME OF DAY =

 0 8 0 0 Local time. The 

hours flash. 

- 3 TIME OF DAY =

 0 8 0 0 Pressing Time of 

Day again confirms changes.

4.4 – Filtration  

XP Controller also allows to create filtering 
systems by using the proper version of the 
SIATA valves. In order for the system to 
work correctly, it is necessary to program 
time to 0 at steps 12 and 13 of Tab. 2 
unless a settling phase is required.   

4.5 – Starting operations  

XP Controller, as well as all SIATA 
controllers, is considered “on service” 
when able to accomplish resins 
regeneration. This is possible ONLY when 
the controller “senses” that the cam is 
correctly positioned at the limit stop. In 
order to perform a few tests before 
installation, it is necessary to connect XP 
Controller to its case in order that the limit 

switch input be correctly closed. With 
reference to what already stated in par. 
4.3, once the XP Controller programming 
has been modified, it is necessary to 
perform a regeneration process in order 
to transfer the new parameters into the 
memory again.   

4.6 – Managing the reserve  

The reserve value programmed through 
steps 6 and 7 of Tab. 2 is subtracted from 
the treatable volume value set through 
steps 4 and 5 of Tab. 2. The result will be 
the available volume. Once the available 

volume is exhausted, a regeneration 
process is performed at the scheduled 
time. If you program 5000 liters of 
treatable volume and 1000 liters of reserve 
volume, the calculated available volume 
will be of 4000 liters.  Available Volume = 
Treatable Volume – Reserve

4.7 – Managing the volume  

Steps 4 and 5 in Tab. 2 describe how to

XP

Siata

318

Содержание PS0335 XP0/05

Страница 1: ...5 V360A XP3 05 PS0025 V132E PS0085 V240A PS0135 V230E PS0150 V250A PS0155 V250A NB PS0165 V260A PS0185 V360A XP CONTROLLER TECHNICAL DATA Power voltage ______________________________230 Vac 10 Network frequency ________________________ 50 60 Hz 3 Power absorbed __________________________________ 4 6 VA Operative temperature _______________________ 0 C 50 C Container dimensions ___________________ ...

Страница 2: ...estremità degli steli c è una parte piatta con due indici Appoggiare il bordo della camme sullo spazio compreso fra tali indici Assicurarsi che gli steli siano orientati verso l interno in modo da accogliere il bordo della camme nel modo migliore Fig 8 Spingere il timer verso la valvola in modo che gli steli rientrino dentro i piloti e i due perni di fissaggio indicati in Fig 7 vadano ad inserirsi...

Страница 3: ...000 litri 7500 500 Si devono trattare 50 000 litri di acqua e se ne vogliono 1000 di riserva Volume 6 50 000 6 8334 nei passi 4 e 5 di tab 2 Riserva 6 1 000 6 166 nei passi 6 e 7 di tab 2 Divisore x 6 AA14x6 AA84 nel passo 8 di tab 2 Nel momento dell entrata in servizio il volume trattabile sarà di 8168 litri 8334 166 Si fa presente che programmare 0000 nel volume significa azzerarlo mentre progra...

Страница 4: ...una modifica al programma originale Siata vengono ricaricati i seguenti parametri di default Ora di rigenerazione 02 30 Giorni di intervallo 7 Volume trattabile 2000 litri Riserva 0000 Divisore 14 imp litro Tempo di lavaggio controcorrente 10 minuti Tempo di aspirazione 30 minuti Tempo di lavaggio lento 20 minuti Tempo di lavaggio veloce 10 minuti Se quanto indicato avviene alla prima accensione d...

Страница 5: ... Installation The controller installation must be performed by qualified technical staff Fig 6 Remove the screw and pull the stems until they reach the position shown below Fig 7 The final part of each stem is flat and has two centering marks Place the cam edge on the space between those marks Make sure the stems are directed inside so as to house the cam edge in the best way possible Fig 8 Push t...

Страница 6: ...ng the AA00 value for the divider means programming the divider as 100 You can treat maximum 70 000 liters water with the SIATA magnetic sensor by programming 10 000 liters for the treatable volume and AA98 for the divider Volume 7 and divider x 7 If you use a counter issuing one impulse every liter or cubic meter the maximum treatable volume will be 1 000 000 liters or cubic meters if you set to ...

Страница 7: ...ble Here the data for the standard Siata Internal program Clock 00 00 Regeneration start time 02 30 Interval between two regenerations 7 Treatable volume 2000 Reserve 0000 Prescaler 14 Power frequency 50 1st phase stop time 10 2nd phase stop time 30 3rd phase stop time 20 4th phase stop time 10 If at the first start of the controller the clock will show 00 00 this means that the battery is down Af...

Отзывы: