6.2.6 – Auto  Manual 

 

When 

Aqua  Ionic 

is  programmed  in  the  Auto  Volume  +  Manual  mode  (this  condition  must  be 

confirmed by the illumination of both LEDs on the panel), the regeneration can be activated only 

using the 

Manual Regen

 key on the panel. When the volume exhausts, the 

Alarm

 output on the 

DIN 360° socket activates (but the corresponding LED on the panel does not illuminate). In this 

mode,  too,  the  timer  performs  its  checks  on  the  probe  reading.  At  the  same  moment  when  the 

conductivity value read by the probe exceeds the programmed set point value and remains above 

that threshold for the whole time which has been set, the alarm will activate (

Alarm

 LED on the 

panel and output signal on the DIN 360° socket). 

 

6.3 – Checking the regeneration efficiency 

 

Pin 3 of the DIN 270° socket, if connected to the ground, enables the regeneration quality check 

which is performed during the last cycle phase. 

Whichever  the  operating  mode  and  the  cause  for  the  regeneration  starting,  during  the  last  cycle 

phase a comparison between the conductivity value read by the probe and the programmed set point 

value occurs; when such a check begins, the 

Int. Alarm

 LED illuminates on the panel.  

If the value read by the probe is lower than the set point value, the last cycle phase is terminated 

before the expiration of the set time, in order not to waste water. The 

Int. Alarm 

LED goes out and 

the controller will immediately start working. 

If, on the contrary, the  value read by the probe remains  above the set  point value for the whole 

duration of the last phase of the regeneration cycle, the 

Int. Alarm

 LED remains on and blocks the 

automatic  performance  of  the  successive  regeneration  cycles,  since  it  is  evident  that  there  are 

problems preventing a correct regeneration performance. Only at this moment the 

Alarm

 output on 

the DIN 360° socket is also activated. 

It is possible to press the 

Reset

 or the 

Manual Regen

 keys to reset the alarm. 

The Reset key allows to restore the correct performance of the regeneration cycles with automatic 

start (which will stop again if the cause preventing the performance of a correct regeneration is not 

identified  and  removed  in  the  meantime),  while  the  Manual  Regen  key  allows  to  immediately 

perform a new regeneration (which will end again with an alarm if, as just mentioned, the cause of 

the previous alarm is not removed). 

 

NOTE:

  In  order  for  this  check  to  be  carried  out,  a  duration  of  at  least  1  minute  must  be 

compulsorily programmed for the last phase of the regeneration cycle, 

step 15, tab. 3

 

Содержание AQUA IONIC

Страница 1: ... di 24 AQUA IONIC USER S AND MAINTENANCE MANUAL y Distributed b 37 Tannery Lane 06 08 Tannery House Singapore 347790 Tel 65 6741 2994 Fax 65 6741 2995 S I A T A Asia Pacific Pte Ltd Distributed by www siata com sg ...

Страница 2: ...EC and that the following harmonized standards have been applied EN 50081 1 Generic Emission Standard Part 1 residential commercial and light industrial premises EN 50082 1 Generic Immunity Standard Part 1 residential commercial and light industrial premises EN 60742 Directions concerning isolation and security trasformers S I A T A S r l has a quality system in accordance with the requirements of...

Страница 3: ... Powering on 10 6 2 Working 10 6 2 1 Auto Set Point 11 6 2 2 Auto Volume 12 6 2 3 Auto Set Point Auto Volume 12 6 2 4 Manual 12 6 2 5 Auto Set point Manual 12 6 2 6 Auto Volume Manual 13 6 3 Checking the regeneration efficiency 13 6 4 Programming 14 6 5 Starting operations 15 6 6 Managing the volume 15 6 7 Installing the probe 16 6 8 Connections 17 6 8 1 Connection of this version to 3 DIN sockets...

Страница 4: ...onic is provided with an eeprom memory where the programming is stored and of a buffer battery allowing to keep the working parameters in the memory in the event of a supply voltage failure Aqua Ionic as well as all the other SIATA controllers is compliant with the EEC Directives and is built in the SIATA factory in Montespertoli Florence Italy working with the Quality System certified according t...

Страница 5: ...n during programming when setting the set point intervention time During operation it illuminates to indicate an alarm condition EXT ALARM It is on when the inhibition signal is present AUTO SET POINT It is on when the regeneration must start because water is not good AUTO VOLUME It is on when the regeneration must start because of exhausted volume MANUAL It is on when the regeneration must not st...

Страница 6: ...t allows to increase the digit blinking on the display When pressed during operation it allows to display the residual volume SELECT It allows to change the regeneration start mode MAN REGEN It allows to activate the regeneration manually RESET During programming it allows to quit without saving the parameter being modified when the key is pressed During regeneration it ends it HIDDEN KEY Placed b...

Страница 7: ...e lot number SN 110 98 the serial number with reference to the code In particular the controller code is composed as follows AI 7 02 05 Controller version assigned by the Technical Office for customizations 05 standard Typology of the electric connections 02 DIN sockets Number of drivers 7 7 drivers Family to which the controller belongs AI Aqua Ionic Fig 2 Fig 2 ...

Страница 8: ...C relative humidity within 30 and 95 5 2 Installation The controller installation must be performed by qualified technical staff the installation procedures must be performed when the device is off power The device consists in an ABS case closed on front by a cover blocked with 4 screws As an optional a transparent cover is available that can be used as a keyboard protection The controller is supp...

Страница 9: ... battery voltage using a multimeter If the measured voltage is less than 3 2 Vdc replace the battery with the spare part code 867 The following servicing operations must always be performed when the controller is off power In case of replacement of the electronic board only and each time you operate on the open case please avoid as much as possible touching the components and the welded parts with...

Страница 10: ...icate that the foreseen conditions have been reached Manual The regeneration starts only when pressing the proper key Auto Set Point Manual The timer performs the checks requested by the Auto Set point mode but it is not able to perform the regeneration in the automatic mode Auto Volume Manual The timer performs the checks requested by the Auto Volume mode but it is not able to perform the regener...

Страница 11: ...illuminates The display is still indicating the conductivity 0 0 5 0 Pressure of the Manual Regen key during operation The regeneration cycle starts even if the controller is inhibited see previous point 1 C 2 6 6 2 1 Auto Set Point When Aqua Ionic is programmed in the Auto Set Point mode this condition must be confirmed by the illumination of the corresponding LED on the panel there is a comparis...

Страница 12: ...to Set Point Auto Volume mode both LEDs on the panel are on both checks indicated in par 6 2 1 and 6 2 2 are carried out The regeneration is activated by the check which as first satisfies the conditions required for the cycle to be started 6 2 4 Manual When Aqua Ionic is programmed in the Manual mode this condition must be confirmed by the corresponding LED on the panel the regeneration can be ac...

Страница 13: ...LED illuminates on the panel If the value read by the probe is lower than the set point value the last cycle phase is terminated before the expiration of the set time in order not to waste water The Int Alarm LED goes out and the controller will immediately start working If on the contrary the value read by the probe remains above the set point value for the whole duration of the last phase of the...

Страница 14: ... C 0 0 The stop of the regenerative cycle second phase 10 PROG MODE 3 C 0 0 The stop of the regenerative cycle third phase 11 PROG MODE 4 C 0 0 The stop of the regenerative cycle fourth phase 12 PROG MODE 5 C 0 0 The stop of the regenerative cycle fifth phase 13 PROG MODE 6 C 0 0 The stop of the regenerative cycle sixth phase 14 PROG MODE 7 C 0 0 The stop of the regenerative cycle seventh phase 15...

Страница 15: ...s the Reset key or to perform a regeneration in order to load the new parameters into the memory 6 6 Managing the volume Steps 3 and 4 of tab 3 describe how to program the treatable volume Using the SIATA Hall effect liter counter the value of the divider AA14 step 5 tab 3 must be set to 14 which means that the available volume is reduced in a not adjustable way by one liter every 14 impulses issu...

Страница 16: ...te that because of the Reed counters characteristics we recommend not to use 1imp 1m3 or similar counters 6 7 Installing the probe The conductivity probe is the most important element of Aqua Ionic and its installation must be performed with the highest care A screened cable is always the best choice to connect the controller to the probe This choice is compulsory when the distance between the con...

Страница 17: ...xample it is the cycle end impulse Please refer to the table of par 6 8 1 to learn which signals are issued by the controller in the Open Collector mode The maximum relay absorbency for the trip coil excitation must be 20mA Here below follow the codes of a few relays that can be used to this purpose all of them with a trip coil to be supplied with 12 Vcd Manufacturer Model OMRON G5V 1 12Vdc TAKAMI...

Страница 18: ...12 Vdc voltage DIN A 1 4 Inhibition signal input when closed DIN A 2 5 Output of the Cycle End Impulse in the Open Collector mode DIN B 4 2 Input of the Remote start signal when closed DIN B 3 2 Input of the regeneration quality control activation signal DIN C 1 4 Output of the Set Point signal in the Open Collector mode DIN C 3 4 Output of the Impulse During Regeneration signal in the Open Collec...

Страница 19: ...at the wires be properly inserted in the 7 pole connector The controller is blocked If you use the side DIN socket check for any short circuited terminals in the connector cap Follow instructions given in par 6 8 The motor does not stop at the limit stop Damages in the plastic components Open the case and check whether the plastic components supporting the micro switch are integer Fig 10 The micro...

Страница 20: ...Aqua Ionic 20 di 24 Fig 10 clearly shows the micro switch its block and command mechanical details and the terminals for connection to the controller Fig 10 Seeger ...

Страница 21: ...otation Please contact the SIATA sales department for further information about the performances that can be obtained with such a modification 4 The plug shaped transformer item 6 can be provided in two ways chlorine timer transformer code 95 STC1 and non chlorine timer transformer code 95 STD The explicit variants concern only the timers with external drivers attachment DA0189 which in the table ...

Страница 22: ...aped transformer 230V 12 V 6 V CHLORINE 95 STC1 7 Ratiomotor 94 R7 8 Timer case kit 81 KIT 9 7 pole connector 93 7 10 Timer supply cable lock 90 11 Micro switch wire 97 12 External cam kit 2221 2 13 Micro switch blocking plate 88 A 14 Microswitch 92 F 15 Microswitch holder 88 16 Aqua Ionic electronic board kit 892 K 17 Cover blocking screw 120 18 Timer case transparent cover 82 19 Stop ring on pow...

Страница 23: ... 17 M A S C H E R I N A POS 16 SOSTITUISCE S r l CODICE DENOMINAZIONE SCALA FIRMA POS 18 POS 15 POS 11 POS 14 POS 13 POS 19 POS 7 POS 12 POS 9 POS 10 POS 8 POS 4 POS 3 POS 6 POS 5 POS 2 POS 1 SCHEMA GENERALE TIMER ELETTRONICO CON N PILOTI ESTERNI Foglio 1 di 1 DA0189 Ing P Meozzi 08 A POS 20 POS 21 ...

Страница 24: ...GRUPPO REVISIONE Foglio 1 di 1 SCHEMA GENERALE TIMER ELETTRONICO CON CAMMA 132 DA0191 Ing P Meozzi 08 A POS 13 POS 18 POS 15 POS 11 POS 14 POS 7 POS 9 POS 8 POS 10 POS 6 POS 21 POS 20 POS 19 POS 22 y Distributed b 37 Tannery Lane 06 08 Tannery House Singapore 347790 Tel 65 6741 2994 Fax 65 6741 2995 S I A T A Asia Pacific Pte Ltd Distributed by www siata com sg ...

Отзывы: