background image

 

2 of 4   

3 of 4 

 

MINI WATER BOOST SYSTEM PERFORMANCE 

(Units tested with 40 psi pre-charge and 20 psi city water pressure)

 

3.  Remove Accumulator air fitting cap and pre-charge with clean pressurized air, or nitrogen. Tank should be 

pre-charged 

at the minimum required pressure of the application

. Replace air fitting cap securely.

 

In most cases 40 psi [2.7 bar] will provide the required pressure at a typical beverage dispense system.  For 
best pump performance, set accumulator pre-charge pressure at approximately 20 psi [1.3 bar] below max. 
pump pressure (as stated on the table), and/or at approximately the pump turn-on pressure. For further 
information consult the factory. 

4.  Turn ON incoming water supply. 
5.  Open the dispenser valves and purge air/water from tubing/accumulator. Close the dispenser valve(s) and let 

the pump fill the accumulator. The pump may not obtain shut-off pressure if excessive air is trapped within 
the system. Repeat this step 2-5 times as necessary, before taste testing. 

 

 

MEDIUM WATER BOOST SYSTEM PERFORMANCE   

(Units tested with 40 psi pre-charge and 20 psi city water pressure)

 

 

 

 

NOTE 1

the accumulator tank pre-charge should 

be checked bimonthly or as necessary.  All outlet 
water pressure must be depleted prior to checking 
or recharging. 
 
 

NOTE 2:

 if subject to freezing temperature, the 

pump, tubing and accumulator tank 

MUST 

be 

drained of all water.

 

MEDIUM WATER BOOST SYSTEM 

(M

EDIUM 

WB 

SYSTEM W

PUMP ON SIDE NOT SHOWN

)

 

 

MAXI WATER BOOST SYSTEM PERFORMANCE  

(Units tested with 40 psi pre-charge and 20 psi city water pressure) 

MINI WATER BOOST SYSTEM 

 

MAXI WATER BOOST SYSTEM 

 

 
 

 

 

 

Отзывы: