SR501 EN Operation Manual
- 38 -
6.10 LWS Preset the water level of water filling when tank is lack of water
Description:
Water level drops from its high level to the low level, when water level is lower
than 20%, then automatic water filling is delayed 30 minutes to start and it fills
water to the preset water level 50% (factory set).
Note:
according to the customer demand, the preset water filling level and
run-on time can be set under menu (detailed see sections 6.10 and 6.11)
Setup steps:
►Select main menu LWS water filling level function
►Press “SET” button, “LWSL” displays and water level
zone”50%” displays also on the screen
►Press “SET” button, “50%” blinks
►Press “▲▼”button to adjust the preset water level, adjustable range is
20-100%, factory set is 50%.
►Press “SET” or “ESC” to confirm
6.11 LWSD delay time of water filling when tank is lack-of water
Setup steps:
►Select main menu LWSD delay time of water filling when tank is lack-of water
►Press “SET” button, “LWSD 30 min” displays on the
screen
►Press “SET” button, delay time “30” blinks
►Press“▲▼”button to adjust the delay time, adjustable range is 0-90-minute,
factory set is 30 minutes.
►Press “SET” or “ESC” to confirm
6.12 OTDI Thermal disinfection
Description:
To avoid occurring bacteria in water tank, controller will trigger the back-up