Pilot Lamp 

Glow Lamp 

Accessory Switch 

Starter Switch 

Ammeter 
Selector Switch 

3-Phase 
Breaker 

1-Phase 
Breaker 

Breaker Trip 
Selector Switch 

Remote Start Terminal 

* Check that 208 V is displayed during operation if using at the three-phase 208 V setting. 
Check that 480 V is displayed during operation if using at the three-phase 480 V setting. The 
voltage of single-phase three-

wire output of “U-W Voltage” is a value that is one half of the 

displayed voltage meter value. 

(2) Ammeter 

Displays the output current (phase current) of the generator. Turn the ammeter selector switch 
to “L1+U” to display the output current of the three-phase L1 phase and single-phase U phase. 
Turn the switch to “L3+W” to display the output current of the three-phase L3 phase and 
single-

phase W phase. “L2” displays the output current of three-phase output terminal L2. 

< Note > 

 If measuring the output current for a single-phase three-wire type, turn the ammeter selector 

switch to “L1+U” or “L3+W”. The voltage cannot be accurately measured if set to “L2”. 

(3) Frequency Meter 

Displays the frequency of the power source. Check that 60 Hz is displayed during operation. 

 

Indicators 

(1) Glow Lamp 

This lamp illuminates when the starter switch is on START 
positon. This lamp turns off when pre-heating is completed.   
This lamp turns off and the generator starts. 

< Note > 

 Pre-heating time depends on the coolant temperature, and 

should be completed in approximately 0 to 16 sec. 

(2) Pilot Lamp 

This lamp illuminates when the engine is operating to indicate 
that power is being generated. 

 

Switches 

(1) Starter Switch 

The engine warms up and starts automatically.   

  START 

The engine is started in this position.   
The engine warms up and starts automatically. 

  STOP 

The engine is stopped, and the power supply 
is turned off completely in this position. You 
can operate the ACCESSORY switch in this 
position.   

 

  AUTO 

The engine is started in this position when the 
REMOTE START terminal closes.

 

 

(2) Accessory Switch 

If you select ON, the display turns on, activate the 
electromagnetic pump, you can check the fuel 
level and you can bleed air from the fuel system. 

Содержание DGK180F

Страница 1: ...birth defects or other reproductive harm Always start and operate the engine in a well ventilated area If in an enclosed area vent the exhaust to the outside Do not modify or tamper with the exhaust s...

Страница 2: ......

Страница 3: ...ration Store this manual in a specified location where it will be secure and available for consulting at any time Order another copy from the authorized distributor where this generator was purchased...

Страница 4: ...6 2 Installation Procedures 23 7 Load Connections 24 7 1 Load Cable Selection 24 7 2 Connecting Load Cables 26 8 Pre Operation Inspection 29 8 1 Checking Engine Oil 29 8 2 Checking Coolant 30 8 3 Che...

Страница 5: ...h as cooling fans and fan belt Always turn the starter switch to the STOP position and stop the engine then close and lock OPERATION PANEL DOOR before checking or maintaining the engine or any equipme...

Страница 6: ...re is no fuel leakage Absolutely never inspect or perform maintenance to the equipment near fire or other open flame Do not put anything other than DEF gasoline diesel fuel etc in the DEF tank Also do...

Страница 7: ...or similar item to avoid any unexpected move when transporting by truck or other vehicle CAUTION PROPERTY DAMAGE Do not use the equipment for any improper applications Improper usage can result in an...

Страница 8: ...Part no X505 010800 Warning Proposition 65 Gen Part no X505 010400 EPA emission complied notice Part no X505 008400 Warning Fire Part no X505 007650 Notice Capacity of the external tank Part no M709 0...

Страница 9: ...Manufacturer 6HK1X ISUZU No of Cylinders bore stroke in mm 6 4 53x4 92 115x125 Continuous Rated Output hp 227 3 Rated Speed rpm 1 800 Displacement cu in liters 475 7 790 Combustion System Direct injec...

Страница 10: ...ability Ambient temperature 5 to 104 F 15 to 40 C Relative humidity 85 or less Altitude 984 ft 300 m or less Power source for submerged pumps and similar civil engineering equipment Power source for l...

Страница 11: ...Fuel Inlet Cover SCR Check Panel Inspection Cleaning Panel DEF Tank Check Panel Tie hole Tie hole Tie hole Engine Check Door Intercooler Drain Plug Alternater Check Door Radiator Intercooler Fan Guar...

Страница 12: ...t Sub Tank Fan Guard Alternater Check Door Fuel Filter Pre Coolant Drain Plug Fuel Filter Main Electromagnetic Fuel Pump Oil Drain Plug Fuel Tank Inside 3way Fuel Valve External Fuel Inlet External Fu...

Страница 13: ...F Level Pilot Lamp Hour Meter Voltage Regulator Glow Lamp Ammeter Selector Switch Starter Switch Breaker Trip Selector Switch Throttle Switch Warning Indicators Accessory Switch SCR Indicators Voltage...

Страница 14: ...d current 5 2 Available Output Monitor The available generated output for each output power source is displayed digitally Note Consider the digitally displayed available output as an approximate estim...

Страница 15: ...e engine will be automatically stopped If this occurs flush the liquid stored in the spill containment Refer to section 10 Inspection Maintenance 15 Flushing Liquid in Spill Containment Note Water can...

Страница 16: ...t battery fluid Refer to section 8 8 Checking the Battery 2 OIL PRESS Engine Oil Pressure Warning Indicator Low Oil Press If the engine oil pressure drops below 7 psi 0 48 x100 kPa during operation th...

Страница 17: ...the engine Contact authorized distributor where the generator was purchased 5 AIR FILTER Air Cleaner Clogging Warning Indicator The AIR FILTER warning indicator illuminates if the air cleaner element...

Страница 18: ...the engine overspeeds the battery voltage is low or some other engine fault occurs during operation If this occurs a malfunction code is displayed on the engine and available output monitors and the e...

Страница 19: ...n LAMP DEF remaining amount DEF LEVEL DEF REFILL DEF NO POWER SHUTDOWN ESCAPE MODE Less than 100 More than 75 All Lamp Turn ON Less than 75 More than 50 4 Lamp Turn ON Less than 50 More than 25 3 Lamp...

Страница 20: ...urn ON Turn ON FORCE PURGE Turn ON Turn ON 3 DEF Indicator This lamp is lit or starts blinking to alert an error relating to SCR system which includes shortfall of DEF using DEF of low quality or disc...

Страница 21: ...e operation panel and tighten the knob Set the ACCESSORY switch to OFF and use the safety cap to cover it Set the STARTER SWITCH selector to START position Note ESCAPE MODE is available for total up t...

Страница 22: ...s the amount of fuel in the tank All lamps are lit when the amount reaches to the maximum level and FULL is lit The lit lamp decreases as the amount of fuel in the tank reaches to EMPTY The fuel level...

Страница 23: ...tch to L1 U or L3 W The voltage cannot be accurately measured if set to L2 3 Frequency Meter Displays the frequency of the power source Check that 60 Hz is displayed during operation Indicators 1 Glow...

Страница 24: ...t followed by the single phase breaker Simultaneous 3 1 The three phase and single phase breakers trip simultaneously 1 3 The single phase breaker trips first followed by the three phase breaker 5 Amm...

Страница 25: ...l fuel inlet and the external fuel return Change the lever of the 3way fuel valve to the A side to supply fuel from the external tank Refer to 9 6 Connecting with External Fuel Tank for corresponding...

Страница 26: ...erator falling No persons should ever be under a lifted generator CAUTION INJURY Always be sure to use lifting hooks when lifting up the generator and raise it slowly at a completely vertical angle Pe...

Страница 27: ...thoroughly inspect and perform maintenance if using in such locations 7 1 Load Cable Selection Select cable for use that has sufficient thickness and an allowable current for use and distance from the...

Страница 28: ...1 0 1 0 150 A 6 2 1 1 0 2 0 3 0 200 A 4 1 1 0 3 0 4 0 4 0 250 A 2 1 0 2 0 4 0 300 A 2 1 0 3 0 4 0 Ex If used voltage is 120 V and voltage drops by 6 V Single phase Cabtyre cables Unit AWG Length 100 f...

Страница 29: ...ten the connection Failure to sufficiently tightened will result in cable burnout Terminal cover must remain closed during operation or breaker will trip 1 Three Phase Output Terminal For three phase...

Страница 30: ...W terminal voltage is 240 V U N terminal voltage is 120 V W N terminal voltage is 120 V For single phase 240 V load For single phase 120 V load Single phase 120V receptacle single phase 240 120V rece...

Страница 31: ...nect an equivalent load between U N and W N If using a single phase three wire output terminal simultaneously with a receptacle output make sure that currents passing through each phase is less than t...

Страница 32: ...ne Oil Use only API service type CJ 4 class 2 Engine Oil Viscosity Grades Use a diesel engine oil with an appropriate viscosity corresponding to the ambient temperature refer to the table WARNING INJU...

Страница 33: ...attach and tighten the radiator cap Attach the radiator plate Note Use GM SPEC 6277M or equivalent Use a 50 50 mix of Long Life Coolant LLC Always use potable water when mixing the coolant Use LLC wit...

Страница 34: ...cking the Fan Belt 1 Fan Belt Tension Press the middle of the fan belt with a force of approx 98N and check whether the amount of deflection is within the range of standard values Standard value amoun...

Страница 35: ...tandardization 22241 standard defined for AUS 32 or the API American Petroleum Institute standards Adding liquids etc other than DEF may result in a malfunction of the SCR system Do not fill with DEF...

Страница 36: ...tinguish between rain water and other liquids Dispose of flushed liquids according to the related laws and regulations 8 7 Checking for Fuel Oil and Coolant Leak Open the check door and check for fuel...

Страница 37: ...down clamp from the battery on the left side Remove the clamp and cable from positive post from the battery on the left side Remove the left side battery from the seat Install the battery by performi...

Страница 38: ...engine contains substances that are harmful to human health Do not direct exhaust fumes at bystanders or buildings WARNING INJURY Always be sure to check that the breakers on load side and switches f...

Страница 39: ...oltage Turn the breakers to ON to start AC power delivery 2 Auto Start Use the VOLTAGE REGULATOR dial to adjust the voltage to the specified value Turn on the three phase and single phase breakers on...

Страница 40: ...power to the three phase output terminal Note If using at the three phase 480 V setting the output voltage of the single phase three wire type is single phase 240 120 V which is the same as the three...

Страница 41: ...the air bleeder plug of the fuel filter sufficiently and operate the priming pump until the fuel comes out Tighten the air bleeder plug and operate the priming pump 10 times or more until the fuel fil...

Страница 42: ...ator will not be used for a prolonged period If you leave the selector in the AUTO or START position the standby current may drain the battery 2 Auto Start The engine stops when the REMOTE START termi...

Страница 43: ...d has exceeded the specified level making it necessary to flush the fluid 7 Spill Containment Fluid Overflow Spill containment accumulated fluid has exceeded the specified level making it near the fil...

Страница 44: ...the B side in order to prevent fuel from flowing out from the external tank fuel inlet return Turn the lever completely as far as possible If the lever is not completely pressed to either side it mig...

Страница 45: ...L DOOR before checking or maintaining the engine or any equipment Use the lifting hook to lift the machines and do not lift up by using other parts Use of such could result in the generator falling No...

Страница 46: ...lated personnel cannot accidentally come close to the generator Close all doors and covers if you are going to be away from this generator Please be careful about a strong wind and the opening and shu...

Страница 47: ...Radiator and Intercooler Clean Valve clearance Check Adjust Supply pump filter Check Clean Fuel injector Check Elimination of carbon in the exhaust pipe line and muffler DEF leakage DEF filter replac...

Страница 48: ...rtly after starting the engine be sure to always check that there is no oil leakage Always be sure to wipe up any spilled engine oil 2 Replacing the Oil Filter Replace Every 500 hours Drain the engine...

Страница 49: ...clips and cleaner cap Remove the outer element Clean or replace the outer element Replace by performing the above procedures in reverse order Note Inner air element must not be reused even if it is c...

Страница 50: ...on the bottom to drain the water When water draining is completed tighten the drain plug on the bottom Tighten the air bleeding plug Drain plug tightening torque 2 3 N m Air bleeder plug tightening to...

Страница 51: ...O ring of the outer case Apply fuel to the each O ring thinly Screw the outer case into the filter by hand until O ring contacts to the sealed surface Fully screw the filter by special filter wrench...

Страница 52: ...no 8981731650 Isuzu part no 9 Engine Supply Pump Strainer Cleaning Replacement Clean Replace Every 500 hours Place a container under Suppuly Pump to catch spilled fuel Remove the joint bolt Clean the...

Страница 53: ...t reusable Reuse may result in failure of the SCR When disposing of discharged DEF comply with regulations Clean the filter by wiping it with clean cloth Refrain from using high pressure air to avoid...

Страница 54: ...radiator coolant drain plug or wrap it in seal tape After the coolant has been drained tighten the coolant drain plug Remove the sub tank and flush the coolant from the sub tank Reattach the sub tank...

Страница 55: ...er and oil has been drained reinsert the drain plug Note After reinserting the drain plug be sure to always check that there is no leakage 15 Flushing Liquid in Spill Containment Check Daily Set a con...

Страница 56: ...uch as indoors or tunnels as the exhaust gas of the engine contains substances that are harmful to human health Do not direct exhaust fumes at bystanders or buildings WARNING INJURY Always be sure to...

Страница 57: ...is running When cleaning be sure to run with the engine stopped Please clean after SCR system temperature drops When high pressure cleaning inside the rear cover is performed please make sure that th...

Страница 58: ...intenance 15 Flushing Liquid in Spill Containment Store in a secured location Clean up all generator components and store in a dry and dust free location Also cover when storing so that rain cannot en...

Страница 59: ...his generator between each generator and set another generator on top of the ties Never stack more than two levels and do not set a generator on top that is larger in weight size than that on the bott...

Страница 60: ...Engine starts but stalls immediately 1 Fuel filter is clogged 2 Water is interfused in fuel line 3 Air is interfused in fuel line 4 Mistake of connecting with external tank 5 Air filter element is clo...

Страница 61: ...voltage 1 Voltage meter is defective 2 AVR is defective 3 Voltage regulator dial is defective 1 Contact distributor or dealer for repair 2 Contact distributor or dealer for repair 3 Contact distribut...

Страница 62: ...59 13 Generator Circuit Diagram...

Страница 63: ...60 14 Engine Electrical Circuit Diagram...

Страница 64: ...61...

Страница 65: ...62...

Страница 66: ...2019...