SRS0 Series

                   

         

   Instruction manual        

ڦ

Product specification code check 

Compare the specification code on the case with the following to make sure it is the product you ordered. 

Ɣ

 Code selection table 

Item 

Code Specification 

1. Series 

SRS1- 

48 × 48  DIN size  Digital Controller 

SRS3 

96 × 96  DIN size  Digital Controller 

SRS4 

96 × 48  DIN size  Digital Controller 

SRS5 

48 × 96  DIN size  Digital Controller 

2. Control output 

Y- 

Contact  240 V AC  2.5 A 

P- 

SSR drive voltage    12 V DC    20 mA   

I- 

Current  4–20 mA  max. 600

ȍ

V- 

Voltage    0–10 V    max. 2 mA 

3. Program 

N None 

1 pattern    10 steps 

4. Event 

1

2 points    240 V AC    1.0 A    Common

5. Remarks 

0 Without 

9 With 

ڦ

Error message 

Screen 

display 

Problem Cause 

Remedy 



(H H H H )  

Higher limit scaleover 

(1) Break in thermocouple input wiring 

(2) Break in RTD input A terminal wiring 

(3) Measured input value exceeded higher limit 

of measuring range by 10%. 

(1) Check thermocouple input wiring for possible break. If there is nothing 

wrong with wiring, replace thermocouple. 

(2) Check RTD input A terminal wiring for possible break. If there is 

nothing wrong with wiring, replace RTD. 

(3) For voltage or current input, check the measurement signal 

transmission unit.   
Check if setting of measuring range code is correct for input signal. 

…………

(L L L L )  

Lower limit scaleover 

Measured input value fell below the lower limit 
of the measuring range by 10%. 

Check for measurement input wiring for reverse polarity or possible   
break, etc. 

žžž

(b - - - )  

Break in RTD input wiring 

(1) Break in B wiring 

(2) Multiple break in ABB wiring 

Check RTD input ABB terminal wiring for possible break. If there 

is nothing wrong with wiring, replace RTD. 

}ƒ

(C J H H )  

Higher limit scaleover of 
cold junction (CJ) of 
thermocouple input 

Ambient temperature has exceeded 80°C. 

(1) Reduce ambient temperature to the level provided in the environment 

conditions for the product. 

(2) If ambient temperature has not exceeded 80°C, inspect the controller.

}ƒ……

(C J L L )  

Lower limit scaleover of 
cold junction (CJ) of 
thermocouple input 

Ambient temperature has fallen below -20°C. 

(1) Reduce ambient temperature to the level provided in the environment 

conditions for the product. 

(2) If ambient temperature has not fallen below -20°C, inspect the 

controller. 

ڦ

Measuring range codes 

Input type 

Code 

Measuring range (°C) 

Measuring range (°F) 

*1 Thermocouple B: Accuracy guarantee is not applicable to 400°C (752°F) or below. 
*2 Thermocouple K (Celsius, Fahrenheit), E, J, T, U:   

Accuracy of indicated values below -100°C and -148°F is ± (1.5%FS + 1 digit). 

*3 Thermocouple PL ll, U: Accuracy of indicated values is ± (1.5%FS + 1 digit + 1°C). 
*4 Thermocouple K (Kelvin) accuracy temperature range: 

10.0–30.0K:  ±(2.0%FS + 1 digit + 1K)  Provided the wire resistance is 10

ȍ

 or below

31.0–70.0K:    ±(1.5%FS + 1 digit + 1K)  Provided the wire resistance is 10

ȍ

 or below

71.0–350.0K:   ±(1.0%FS + 1 digit + 1K)   

*5 Thermocouple AuFe, Cr: Accuracy of indicated values is ± (1.0%FS + 1K). 
*6 Thermocouple B, T: Accuracy of indicated values below these temperatures is 

subject to wire resistance below 50

ȍ

:

B: 500°C (930°F) 
T: -240°C (-400°F) 

*7 Temperatures below -273°C (-459°F) are subject to scaleover display. 
*8 With or without a decimal point is selectable for TC and Pt. 

Note: Unless otherwise designated, the factory default settings are as follows: 

Input range  Standard/rating Measuring range

Multi-input Thermocouple 

K

0–1370°C 

Multi-

in

put

T

h

ermo

co

up

le

B                  *6 

h

i

      *1 

0–1800°C 0–3300°F 

R

hj

-50–1700°C 0–3100°F 

S

hk

0–1700°C 0–3100°F 

K

hl

      *2 

-199.9–400.0°C -300–750°F 

hm

0–1370°C 0–2500°F 

E

hn

      *2 

0–700°C 0–1300°F 

J

ho

      *2 

-200–600°C -320–1100°F 

T                  *6 

hp

      *2 

-270–400°C -450–750°F 

N

hq

0–1300°C 0–2300°F 

PL ll             *3 

ih

0–1300°C 0–2300°F 

WRe5-26  

ii

0–2300°C 0–4200°F 

U                  *3 

ij

      *2 

-199.9–400.0°C -300–750°F 

L                 

ik

0–600°C 0–1100°F 

Kelvin

K

il

      *4 

10.0–350.0K 

AuFe-Cr

im

      *5 

0.0–350.0K 

RTD

 Pt100 

kl

-199.9–300.0°C -300–600°F 

mV

-10–50 mV 

oj

Scaling range: -1999–9999      Span: 9999 digits 

ڦ

Names and functions of parts on front panel 

(1) Measured value (PV) display 

(2) Target set value (SV) display 

(3) Action display 

(4) Operating keys 

Name

Function

(1) Measured value (PV) display  1) Measured value display LED (red) 

• Displays current measured value (PV) on basic screen (screen 0-0). 

• Displays type of parameter on each respective parameter display screen. 

(2) Target set value (SV) display  2) Target value display LED (green) 

• Displays current target value (SV) on basic screen (screen 0-0). 

• Displays set values on each respective parameter setting screen. 

(3) Action display 

Displays status of controller. 

• RUN: Action display LED (green) 
 

Off:   

   Control halt status (STBY or RST) 

 

On:   

   Running by fixed value control status (FIX) 

 

Flashing:   Running by program control status (RUN) 

• OUT: Control output (green) 
 

For output by contact or SSR drive voltage: 

 

Off:   

   Output is OFF. 

 

On:   

   Output is ON. 

 

For voltage/current output: 

 

Off when output is 0% and On when output is 100%.   

 

In other cases, flashes at intervals of 0.5 seconds (multiples of 0.5 sec.). 

• AT: Auto tuning LED (green) 
 

Off:   

   Auto tuning not executed 

 

On:   

   Auto tuning standby 

 

Flashing:   Auto tuning being executed 

• MAN: Manual control LED (green) 
 

Off:   

   Automatic control operating status 

 

Flashing:   Manual control operating status 

• EV1: Event output 1 (orange) 
• EV2: Event output 2 (orange) 
 

Off:   

   Event output is OFF. 

 

On:   

   Event output is ON.

(4) Operating keys 

    : Parameter key 
 

Displays the next screen in various screen groups. 

        : Down key 
 Decrements 

set 

values. 

        : Up key 
 Increments 

set 

values. 

    : Entry key 
 Confirms 

set 

values. 

 

Displays various screen groups if no SV values are being modified on   

 

the basic screen. 