background image

19 

16. Trouble Shooting

 

 

In the event a problem arises during operation, inspect the instrument by referring to the following table and call our office in the neighborhood. 
 

 

Problem 

Point to be inspected 

Remedial measure 

Output has stopped.  1) Alarm monitor O.C. lights. 

It appears that excessive current flowed for some reason. For pure metal 

heater or transformer load, set longer soft start time. If alarm lights 
again, turn power off to bring power regulator to 0%. Then, turn power 

on again. 

 

2) Alarm monitor O.H. lights. 

Thyristors might be overheated. Turn power off to lower instrument 

temperature and turn power on again. If monitor lights again soon after 
situation is normalized, too large load current of thyristor or poor heat 

radiation is suspected. Use with reduced load current or improve radiation 
conditions. 

 

3) Alarm monitor FUSE lights. 

Rapid fuse for thyristor protection might be fused. See if there is short-circuit 
of  load  or  ground  fault  and  replace  with  new  fuse  after  removing  cause  of 

problem. 

 

4) Alarm monitor THY lights. 

If load current is zero, load is open. Check for break of load. 

 

5) PL lamp (green) does not 
light. 

Examine power supply and check the power source side if power is off. In 
case power is on, instrument trouble is suspected 

 

6) Are control input signals being 
received? 

Measure input level across terminals C1 and C2 by using a tester, for 
example. If there is no input signal, check the supply source of signal such 

as a controller. In case regular signal is found, check connection and set 
values of power regulators. When they are correct, instrument trouble is 

suspected. 

Output 

keeps 

being produced. 

1) Alarm monitor THY lights. 

Thyristor short-circuit or open load is assumed. 

 

2) Is load circuit open? 

When load circuit is open, panel meter and tester will show high voltage. 

Examine load circuit. (This sometimes happens during trial run.) 

 

3)  Base  power  or  low  power 

regulator is connected. 

It is for preventing minimum value of output from being 0. 

Detach low power regulator and recheck. 

Maximum  output 

has lowered. 

1) Check settings on scales of 

various power adjusters. 

Check scales of internal and external power adjusters. Set at 100% and 

see how output will change. 

 

2) Check control input signal 

Check if control input signals have been received hundred percent. 

 

3) Addition of current limiting 
circuit. 

Examine scale of current limit setting device. Set at 100% and confirm 
output voltage/current. If output current flows fully at rated level, current 

limiting function is working. 
Load is far heavier than rated for PAC27. 

 

4) Constant power (power FB) 
control 

Rated voltage x rated current x 1/2 should be in proportion to control 
input signal. Measure output current. If more current than 1/2 of the 

rating flows, maximum output will fall. 

 

5) Check output voltage meter. 

Indicated value may change depending on types of meters. Make sure 

to use true RMS type or movable iron piece type meter. When voltage 
is measured by using general digital or analogue tester, average value is 

converted into true RMS for display. Hence display error increases. (In the 
case of 200 V power supply, display error will come to 43 V maximum. 

Fuse breaks 
(FUSE  lights)  or 

excessive  current 
protective  circuit 

(O.C.) is activated 

frequently. 

1) Are load capacity and PAC27 
capacity suitable? 

In case load rate exceeds 100%, output should be lowered by the use of 
power adjuster. 

2) In the case of load with large 
rush current such as pure metal 

heater. 

Set longer time for soft start. If it does not work, add current limiting 
function (option) or replace PAC27 with one which has a larger current 

rating. 

3) Transformer is used. 

Set longer time for soft start. Try to reduce load relatively to transformer 

capacity. If noise is assumed to be cause of erroneous operation, connect 
capacitor (250V AC 0.1 μF) across terminals R and T. 

 

 

Содержание PAC27

Страница 1: ...to get into the product If something gets in by mistake and it is necessary to insert your hand or tool inside it make sure to turn the power off and to confirm that the condition are safe enough to...

Страница 2: ...2YHUKHDWLQJ ODUP 7K ULVWRU 7URXEOH ODUP 3RZHU GMXVWPHQW DQG 6RIW 6WDUW 7LPH GMXVWPHQW QWHUQDO 3RZHU 5HJXODWLRQ 6RIW 6WDUW 7LPH GMXVWPHQW 9DULRXV KDUDFWHULVWLFV XUUHQW DSDFLW DQG DORULILF 9DOXH PELHQW...

Страница 3: ...3 1 Confirmation of Specification Codes Please double check that the delivered product is exactly as you specified If you need further information please get in touch with our nearest local office...

Страница 4: ...er adjuster SOFT START Soft start time adjuster HEATER SET Heater setting device for heater break alarm option H B SET Heater break alarm setting device option Terminal marking and description C1 C2 C...

Страница 5: ...perature which exceeds 40 C Temperature allowed for this instrument is below 50 C 2 Humidity which exceeds 90 RH 3 Flammable gas corrosive gas or gas or particles that can deteriorate electrical insul...

Страница 6: ...as to keep it from easy contact with persons It has to be installed vertically for heat radiation leaving more than 100 mm spaces above and below it respectively If it is inevitable to install the in...

Страница 7: ...7 6 Circuit Block Diagram and Terminal Marking Terminal Marking Control Terminal No 1 18 See Page 4 2 2 Power Load Circuits...

Страница 8: ...ity When T terminals are wired use wire material of 0 5 mm2 minimum 8 Wiring for Control Signals For control signals M3 5 terminal screws are used Use a crimp style terminal of more than 3 5 mm in ins...

Страница 9: ...d temperature blocks the gate signal of the thyristor and stops output at which time current flows across the alarm output terminals AL1 and AL2 The monitor lamp O H lights The normal state is restore...

Страница 10: ...fect of suppressing the rush current of a heater Setting is possible from less than one second min to more than 30 seconds max The longer the set time the slower the response of output Time should be...

Страница 11: ...In case ambient temperature exceeds 50 C the instrument should be used with load current as illustrated below 11 3 Control System and Output Waveform 11 4 Special Heater and Feedback Control Type of h...

Страница 12: ...dealing with low voltage command When power line is wired as a precaution against accidental short circuit make sure to install one molded case circuit breaker for each PAC27 The current capacity of...

Страница 13: ...h a thyristor In case an ordinary transformer is used no problem will be caused when the load rate is held below 70 of the rating for the transformer 13 2 When Electromagnetic Switch Contactor Is Used...

Страница 14: ...operation manual power adjuster switch is used voltage current input type 14 1 4 External power Base residual power adjuster 14 1 5 Contact input High low power adjuster When an external power adjust...

Страница 15: ...ssumption that voltage and current have similar waveforms Depending on the types of loads however voltage has a waveform which is different from or out of proportion to that of current If this is the...

Страница 16: ...sed for almost all types of heaters and allows for precision control of temperature As the constant power control is meant for a heater load a correct power level is unable to be attained for other lo...

Страница 17: ...imiting works at 0 of the rated current and no output is produced If the instrument is used without the current limit setting device the control terminals CL2 and CL3 have to be short circuited Then t...

Страница 18: ...m with no condensation Storage temperature between 20 and 65 C Applicable standards Safety IEC 60947 4 EN60947 4 EMC EN60947 4 EMC immunity EN60947 4 on condition that designated noise filter is used...

Страница 19: ...ne load circuit This sometimes happens during trial run 3 Base power or low power regulator is connected It is for preventing minimum value of output from being 0 Detach low power regulator and rechec...

Страница 20: ...Specialists Head Office 2 30 10 Kitamachi Nerima ku Tokyo 179 0081 Japan Phone 81 3 3931 7891 Fax 81 3 3931 3089 E MAIL exp dept shimaden co jp URL http www shimaden co jp The contents of this manual...

Отзывы: