background image

No. 2

Cable

Color and Signal

Connector

GAT10-DN

DeviceNet Specifications

Transmission rate

125k bps
250k bps
500k bps

Setting not allowed

DeviceNet transmission rate setup

RS-485 (Shimaden standard protocol) Specifications

Specifications

EIA RS-485 compliant
2-line half duplex multidrop
Start-stop synchronization
Max. 500 m
19200 bps
7 bit/even parity/1 stop bit

Max. 8

SR80 series, SR90 series, SR253, SD16, EM70, FP93

Approx. 1.5 sec
(when 8 Shimaden units are connected and without SV
value updating, and parameter reading/writing)

Terminal arrangement

Use the special cable for DeviceNet.

Use the attached connector.

The connector is equivalent to the MTB2, 5/5-ST-5. 08 ABGYAU made by PHOENIX CONTACT.

For grounding and terminating resistor for DeviceNet, refer to the DeviceNet Specifications published by
ODVA.

4. Wiring

Connecting DeviceNet communications

Item

Signal level
Communication method
Synchronization method
Communication distance
Communication rate
Data format

Number of connectable
Shimaden instrument

Connectable products

Scan time

Connecting RS-485 communications

RS-485

Power supply

Terminating resistor

(attached to the instrument)

Shimaden instruments

No particular maintenance is required for the GAT10-DN. Check the inspection items listed in Master
PLC User's Manual so that your system can always be used in optimal conditions.

Maintenance

The external line should not be bundled with or installed adjacently to a load line except tho se from
the main power circuit line, a high voltage line and the PLC. Otherwise it will easily be affected by
noise, surge or induction.

For a shielding wire or a shielded cable, one-point grounding on the PLC side is required. Depending
on the condition of external noise, however, it may be better to ground on the externa l side.

1 to 8

Local address

Connector
Network current consumption

Special cable for DeviceNet

125k bps

500k bps

250k bps

500 m

100 m

250 m

Specifications

Master/slave system
CAN Protocol
Trunk line, Drop line
125k/250k/500k bps

Fixed to 24 words each for input and output
0

63

Communication adaptor

Accessories
40mA max.

Item

Communication system
Protocol
Type of transmission line

Type of device
Occupied word count
Node address

Maximum transmission
distance

Connecting cable

Transmission rate

SW6

OFF

ON

OFF

ON

SW7

OFF
OFF

ON
ON

DeviceNet Node Address Setup

NA0

Address

0
1

・・・

62
63

NA5

NA4

NA3

NA2

NA1

OFF

OFF

OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

・・

・・

・・

・・

・・

・・

ON

ON

ON

ON

ON

ON

2

ON

ON

OFF

OFF

OFF

OFF

External Wiring

As one of the requirements for enabling the GAT10-DN to function thoroughly and to establish a
highly reliable system, external wiring that is not easily affected by noise is necessary. The following
are matters to be attended to for external wiring.

Signal

V-

CAN_L

Drain

CAN_H

V +

Color
Black

Blue

----

White

Red

The GAT10-DN has a built-in RS-485 terminating resistor. To the Shimaden instrument as the final
station, attach the terminating resistor supplied as an accessory to it. However,  please attach the
terminating resistor to only one instrument (final station). If attached to two or more i nstruments,
correct operation cannot be guaranteed.

Note: No devices except Shimaden instruments should be connected to the RS-485 line. Otherwise,

correct operation cannot be guaranteed.

Note: Make sure to use GAT10-DN as a terminal station of RS-485 communications.

Terminating resistor

DeviceNet

RS-485

Install the DeviceNet terminating resistor according to the Master PLC Instruction Manual and  the
DeviceNet Specifications issued by ODVA.

Transmission rate

Total length

GAT10-DN

SHIMADEN

POWER

RESET

MS

NS

RX

TX

LED indicating operating status of DeviceNet

LED indicating operating status of RS-485
communication

Reset switch

Switch for transmission rate setup

( SW6, SW7 )

Note: Set values become effective upon applying 

power

 or resetting.

DeviceNet
connector

V-

CAN_L

CAN_H

Drain

V+

Switch for node address setup

( NA0

NA5 )

Lights "green" when GAT10-DN
operates normally. In other displays,
setting error/device error has occurred.

Name

Color

Function

Remarks

MS

Green/

Red

Module status
(DeviceNet)

Lights "green" when GAT10-DN is on-
line. In other displays, communication
failure/connection error has occurred.

NS

Green/

Red

Network status
(Device Net)

Lights during reception of data

TX

Green

RS-485
Data transmission

Lights during transmission of data

RX

Green

RS-485
Data receipt

LED indicating operating status

V -

CAN_L

Drain

CAN_H

V +

V -

CAN_L

Drain

CAN_H

V +

Name of Signal

No.

RS-485

: -

RS-485

: +

NC

Power supply: N
Power supply: L

Power supply: FG

RS-485

: SG

NC

L

N

⑦ ⑧

④ ③


No. 1

+
-

SG

+

-

SG

No. N

(the final station)

+

-

SG