_________________________Shihlin Electric SPM-3 User Guide__________________
12
N7: CT Primary Setting from 1-5000 (Default 1)
N7
CT1
0001
N8: CT Secondary Setting from 1-5 (Default 1)
N8
CT2
1
N9: BACK LIGHT TIME OUT Setting from 0-120 minutes (Default 1) .
If 0 is chosen, the back light will always be ON. Press any key to turn on back light.
N9
BACK
LIT
120
N10: BACK LIGHT LEVEL Setting from 0-4 (Default 3).
If 0 is chosen, the back light will always be OFF.
N10
BACK
LIT
LVL
3
N11: I-1 Current Direction Setting - “Positive” or “Negative”. (Default POSITIVE).
If the current is connected in wrong direction, select “Negative” to correct the display
value.
N11
I-1
POSITIV E
N12: I-2 Current Direction setting - “Positive” or “Negative”. (Default POSITIVE).
If the current is connected in wrong direction, select “Negative” to correct the display
value.
N12
I-2
POSITIVE
N13: I-3 Current Direction setting - “Positive” or “Negative”. (Default POSITIVE).
If the current is connected in wrong direction, select “Negative” to correct the display
value.
N13
I-3
POSITIVE
N14: V1(V12) Voltage Eligibility Rate Upper Limit Setting from 0-65535 (Scale 0.1, refer to
Secondary) (Default 65535)
N14
U1
UP
LMT
65535
N15: V1(V12) Voltage Eligibility Rate Lower Limit Setting from 0-65535 (Scale 0.1, refer to
Secondary) (Default 0)
N15
U1
LOW
LMT
00000