Analog input and output parameter group 02
PARAMETER DESCRIPTION 84
Terminal 3-5 disconnect function
1)
If 02-24(P.184) = 0, after disconnection, inverter will slow down to 0Hz, and after reconnection, the inverter
will accelerate to current given frequency.
2)
If 02-24(P.184) =1 after disconnection, inverter will slow down to 0Hz and at the same time multi-function
digital output terminal will set off an alarm; after reconnection, alarm will be released and the inverter will
accelerate to the current given frequency.
3)
If 02-24(P.184) =2 after disconnection, the keypad will display “AEr” alarm, inverter will stop immediately, and
reset is required to release the alarm.
4)
If 02-24(P.184) = 3, after disconnection, the inverter will continue to run according to the frequency command
before disconnection, the multi-function digital output terminal will set off an alarm, which will be released
after reconnection.
Note:When 02-20(P.17)=1, 2, terminal 3-5 is voltage signal setting, this disconnection function will be invalid.
Terminal 3-5 current/voltage input
Terminal 3-5 cannot receive negative voltage and the minimum input is 4mA when selecting current input.
Note: The function of terminal 3-5 here must first switch AVI-ACI to the corresponding position and make sure it
matches the setting value of 02-20 (P.17).
5.3.4 Inverter rated current display level
Parameter
Name
Default
Setting Range
Content
02-52
P.56
Inverter rated current
display level
Note
0~500.00A
---
Display level
Used for inverter current output display.
Note: The default value of parameter 02-52 (P.56) is determined by the model.
5.3.5 PWM signal duty cycle
This parameter is used to set the period of the PWM signal input to the STF terminal.
Parameter
Name
Default
Setting Range
Content
02-63
P.204
PWM signal duty
cycle
0
0
Automatically detects the period of PWM pulse input
into terminal STF
1~1000ms
1~1000ms: Set the PWM duty cycle value input into
terminal STF
PWM signal duty cycle
1. When 02-63 (P.204) is set to 0, SL3 automatically detects the period of PWM signal input to
terminal STF.
2. When 02-63 (P.204) is set to a value other than 0, when the period of PWM signal that actually input to terminal STF
is not the same as 02-63 (P.204) value, it will cause an error in the output frequency calculation.
3. The PWM signal reference frequency function is only applicable to terminal STF (03-00 (P.83) needs to be set to 41).
For details, refer to chapter 5.4.1.