Operation modes of inverter
BASIC OPERATION 31
4.2 Operation modes of inverter
Operation modes are related to signal source for the target frequency and signal source for motor starting. In
Shihlin SL3 inverter there are nine kinds of operation modes: “PU mode(
)”, “JOG mode(
)”, “External
mode(
)”, “Communication mode (
)”, “ Combined mode 1 (
)”, “ Combined mode 2(
)”, “ Combined
mode 3(
)”, “ Combined mode 4(
)”, “ Combined mode 5(
)”.
You can use the built-in keypad to monitor output frequency, monitor output voltage, monitor output current,
browse alarm messages, parameter settings, and frequency settings. There are 6 working modes in the built-in
keypad: "Operation Mode", "Monitoring Mode", "Running Direction Setting Mode", "Frequency Setting Mode",
"Parameter Setting Mode", and "HELP Mode".
Related
parameters
Value
Operation
mode
Signal source for target frequency
Signal source for motor
starting
Remarks
Operation
mode
selection
00-16(P.79)
0
PU mode
(
)
Built-in keypad
button on built-in keypad
“PU mode”, “JOG
mode” and
“external mode”
are
interchangeable.
JOG mode
(
)
Value set in parameter 01-13(
P.15)
button on built-in keypad
External mode
(
)
“External voltage/current signal”,
“multi-speed terminal” and external
JOG signal (01-13(P.15))
External
STF/STR terminals
Frequency of each section in the
programmed operation mode 04-19~
04-26 /
P.131~P.138
External STF terminal
1
PU mode
(
)
Equals to “PU mode” when 00-16(P.79
)
=0
“PU mode” and
“JOG mode” are
interchangeable.
JOG mode
(
)
Equals to “JOG mode” when 00-16(P.79)=0
2
External mode
(
)
Equals to “External mode” when00-16(P.79)=0
3
Communication
mode
(
)
Communication
Communication
4
Combined
mode 1 (
)
Built-in keypad
External STF/STR terminals
5
Combined
mode 2 (
)
External voltage / current signal,
multi-speed terminal
button on built-in keypad
6
Combined
mode 3 (
)
Communication, multi-speed terminal
and external JOG (01-13(P.15))
External
STF/STR terminals
7
Combined
mode 4 (
)
External voltage / current signal,
multi-speed terminal
Communication
8
Combined
mode 5 (
)
Built-in keypad, multi-speed terminal
and external JOG (01-13(P.15))
External
STF/STR terminals
When 00-16(P.79)=0, the external mode (
) is the default mode after inverter is turned on. Use
00-16(P.79) to switch the operation mode.