INSTALLATIEHANDLEIDING – P15
VERSION 0129NM02INT01
MANUEL D’INSTALLATION – P15 |
P15
EN
NL
FR
DE
091NM20INT04
5.4 OPTIONAL TETHERED CABLE
Step 1: Select the appropriate grommet to suit the cable
thickness and place it in the opening of the power cable
inlet. Lubricate if necessary to make it easier to feed the
power cable through
Step 2: Detach the DC protection module and carefully
put the phase wires (brown, black and grey) and neutral
(blue) of the tethered cable one by one through the
module
Step 3: Connect the tethered cable wires on the relays,
PE cable on the terminal block, and car-communication
wire (red wire), like indicated in the ‘3.4.2 Overview
Tethered Cable Connections’ section
Step 4: Take the DC-protection module and attach the
DC-protection module cable to the PCB.
5.5 COMMUNICATION CONNECTION PRO
For Ethernet or NewMotion mobile router connection
(preferred) proceed with 5.5a, for GPRS connection
proceed with 5.5b.
5.5A BUSINESS PRO COMMUNICATION
CONNECTION(S) (UTP)
Step 1: Feed the UTP cable(s) through the rubber stop(s)
on the data cable inlet and then connect it to the left
Ethernet port(s), like indicated in the ‘3.4.1 Overview of
Connections’ section
Step 2: Connect the UTP cable to a internet enabled
router with DHCP or NewMotion mobile router.
5.5B BUSINESS PRO COMMUNICATION
CONNECTION(S) (GPRS)
Step 1: Check and make sure signal strength is sufficient
5.6 COMMUNICATION CONNECTION
BUSINESS LITE
For Daisy chain configuration proceed with 5.6a, for Star
configuration proceed with with 5.6b.
5.6A BUSINESS LITE COMMUNICATION
CONNECTION (DAISY CHAIN CONFIGURATION)
Step 1: Feed the UTP cable(s) through the rubber stop(s)
on the data cable inlet and then connect it to the left
Ethernet port(s), like indicated in the ‘3.4.1 Overview of
Connections’ section.
The other end should be connected to the right hand
side Ethernet port of the Business Pro.
Step 2: Feed a cable from right hand side port of
the Business Lite to the left Ethernet port of the next
Business Lite.
Repeat Step 2 until all Lites have been connected.
5.6B BUSINESS LITE COMMUNICATION
CONNECTION (STAR CONFIGURATION)
Step 1: Business Pro: Feed a UTP cable(s) through the
rubber stop(s) on the data cable inlet and then connect
it to the right Ethernet port(s), like indicated in the ‘3.4.1
Overview of Connections’ section
Step 2: Business Pro: Connect the UTP cable to a switch
(no DHCP)
Step 3: Business Lite: Feed a UTP cable(s) through the
rubber stop(s) on the data cable inlet and then connect
it to the left Ethernet port(s), like indicated in the ‘3.4.1
Overview of Connections’ section
Step 4: Business Lite: Connect the UTP cable to a
switch (no DHCP).
5.7 FINISHING UP (CLOSE ENCLOSURE)
Step 1: Check and make sure that the rubber seal is
properly in place on the edge
Step 2: Place the cover on the charge point
Step 3: Hand-tighten the four M4 x 12 mm bolts provided
around the socket so that the cover closes on the rubber
seal but the rubber seal does not deform
Step 4: Hand-tighten the other two M4 x 12 mm bolts
provided in the bottom of the cover
Step 5: Turn the socket lid clockwise in the cover and
hand-tighten the M4 x 20 mm bolt provided
Step 6: Switch on power to the charge point
Step 7: Wait until charge point is fully started up (+/-10
minutes, LED should be off)
Step 8: Check that the business Pro is connected to the
network. A quick check can be done online via
http://chargeportal.newmotion.com/test
. Simply
enter the serial number into the search field and click
“Search”. ‘Online’ should appear after the serial number.
Step 9: Check if the Business Lites are
connected online. Check all Business Lites on
http://chargeportal.newmotion.com/test
. ‘Online’
should appear after entering the serial number. If ‘Online’
does not appear, check whether the charge point is
properly connected and reset the Business Lites while the
Business Pro stays powered on.
Step 10: If configuration of charge point power settings
is needed (for example lower amperage settings) please
contact NewMotion.