Electrical Specifications
33
5
Technical Specifications
➣
In this chapter…
page 33
page 34
page 34
page 35
5.1
Electrical Specifications
Operating Voltage
: 18–32VDC
Power Consumption
:
Max. 16mA in standby
Max. 40mA in alarm
Electrical Outputs
Dry Contact Relays:
Table 11: Contact Ratings
Relay Name
Type
Normal
position
Maximum
Ratings
Alarm
SPST
N.O.
2A at 30VDC
Fault
*
SPST
N.C.
2A at 30VDC
*
The fault relay is normally energized and the contact is closed during
normal operation of the detector. The contact is open at fault condition or
low voltage.
0–20mA current output:
The 0–20mA is source option only.
The maximum permitted load resistor is 600ohm.
Table 12: 0–20mA Current Output
State
Output
Fault
0 + 0.5mA
Bit Fault
2mA±10%
Normal
4mA±10%
Warning
16mA±5%
Alarm
20mA±5%
Содержание 20/20MPI
Страница 2: ...www acornfiresecurity com www acornfiresecurity com...
Страница 12: ...www acornfiresecurity com www acornfiresecurity com...
Страница 14: ...www acornfiresecurity com www acornfiresecurity com...
Страница 18: ...www acornfiresecurity com www acornfiresecurity com...
Страница 24: ...www acornfiresecurity com www acornfiresecurity com...
Страница 32: ...www acornfiresecurity com www acornfiresecurity com...
Страница 36: ...www acornfiresecurity com www acornfiresecurity com...
Страница 48: ...www acornfiresecurity com www acornfiresecurity com...
Страница 52: ...www acornfiresecurity com www acornfiresecurity com...
Страница 53: ...Appendix 53 Appendix www acornfiresecurity com www acornfiresecurity com...
Страница 54: ...www acornfiresecurity com www acornfiresecurity com...
Страница 58: ...www acornfiresecurity com www acornfiresecurity com...