background image

10

SJ-V35L
SJ-V39L

2. DEFROSTING

(1) No defrosting operation is necessary

No defrosting operation is necessary.
As this machine is so designed that a built-in
evaporator cools air and a fan circulates cooled
air, neither the freezer nor the refrigerator is
frosted, though the evaporator is frosted.
The frosted evaporator is defrosted automatically
due to the function of defrosting timer and heater,
requiring no defrosting operation.

(2) Where is melted frost brought

1. Melted frost is brought into the evaporating

pan at the bottom of the set and is evaporated
here by the heat of sub condenser.

2. Be sure to use the evaporating pan as inserted

so as to be level with the outer case.

(3) The following circuit diagrams in the table show automatic defrosting function of the refrigerator with

timer and defrost thermostat.

Operation

Electric diagram

Description

1. Cooling
    (Normal)

2. Defrosting
  

(Time 20 to 30 min.)

3. Drain

(Time approx. 5 min.)

4. Cooling (start)

The integration timer integrates running
time of the compressor. When it reaches
cycle time of defrost timer, the timer 
contact is changed to start defrosting.

When the defrost thermostat becomes
OFF, the timer motor at rest starts running.
During the operation time (delay time of
defrost timer), defrosted water is drained 
outside the refrigerator.

Timer contact is changed to cooling 
operation and the compressor starts 
running and the timer motor stops.
Defrost thermostat contact becomes ON
when it’s cooled. And the timer moter
starts running. (Figure F-4.)

Figure F-4.

Figure F-5 .

Figure F-6.

Figure F-7.

TM

COMP

Defrost thermostat ON

Compressor running

Timer motor running

Timer contact

Defrost 
thermostat (ON)

Compressor

Timer motor

SOURCE

TM

COMP

Defrost thermostat OFF

Compressor running

Timer motor running

Thermostat

Timer contact

Defrost 
thermostat (OFF)

Compressor

Timer motor

SOURCE

TM

COMP

Defrost thermostat OFF

Compressor stops

Timer motor running

Thermostat

Timer contact

Defrost 
thermostat (OFF)

Compressor

Timer motor

SOURCE

TM

COMP

Defrost thermostat ON

Compressor stops

Timer motor stops

Thermostat

Timer contact

Defrost 
thermostat (ON)

Compressor

Timer motor

SOURCE

Thermostat

The timer contact is changed to start
defrosting, the timer motor stops, and
power is supplied to the defrost heater.
It takes about 20 to 30 min. to defrost.
When little frosted the defrosting takes
little time.  When much frosted, the
defrosting takes much time.

Defrost heater 

Thermo. fuse

Defrost heater 

Thermo. fuse

Defrost heater 

Thermo. fuse

Defrost heater 

Thermo. fuse

Содержание SJ-V35L-GY

Страница 1: ...y safety regulations in some countries the set should be restored to its original condition and only parts identical to those specified should be used MODELS TABLE OF CONTENTS page SPECIFICATIONS 2 DESIGNATION OF VARIOUS PARTS 4 LIST OF ELECTRICAL PARTS 6 WIRING DIAGRAM 7 FUNCTIONS 9 DEODORIZING OPERATION 12 ASSEMBLING PROCEDURES OF MAIN PARTS AND CAUTIONS 13 COOLING UNIT 18 REPLACEMENT PARTS LIST...

Страница 2: ...u ft V 86 liter 3 0 cu ft V 86 liter 3 0 cu ft Defrosting System Heater system Start Automatic Finish Automatic Temperature control Automatic Adjustable No frost freezer Yes Interior lamp 1 Caster 4 Evaporating pan 1 Freezer Freezer shelf 2 Compartment Freezing room 1 Ice cube maker 1 Ice cube box 1 Freezer pocket S 1 Freezer pocket L 1 Refrigerator Chilled case 1 Compartment Refrigerator shelf S ...

Страница 3: ...Climate class T Rated input W 139 145 165 175 Rated input of heating elements W 128 152 Defrosting input W 128 152 Refrigerant Charging quantity HFC 134a 115g HFC 134a 120g Net weight kg 69 73 COLOR Items SJ V35L GY SJ V39L GY Outside color Gray Inside color White Source cord 2pin Plug type A 1 ...

Страница 4: ...zer pocket L F door pocket L HS 18 Magnetic door seal Door packing 19 Egg holder S Egg tray 20 Egg holder L Egg tray 21 Egg pocket Door pocket HS 22 Utility pocket Door pocket HS 23 Utility pocket Door pocket S HS 24 Small pocket Dressing pocket 25 Fan light switch 26 Bottle pocket S Bottle pocket S 27 Bottle holder Bottle guard 28 Bottle pocket L Bottle pocket HS The names in parenthesis are the ...

Страница 5: ...t R C box Multi louver Protect cover Starting relay Overload relay Compressor Door switch 2P Door switch 3P Mark Cold air flow Figure D 2 SJ V39L Fan motor Left F thermostat Right Evaporator Defrost thermostat Defrost heater Damper thermostat R C box Multi louver Protect cover Starting relay Overload relay Compressor Door switch 2P Door switch 3P ...

Страница 6: ...r switch PS100 01T 250V 0 5A 2 terminals type push button Freezer compartment Door switch PS100 T 250V 0 5A 3 terminals type push button Refrigerator compartment Fan motor 3R00044B 220 240V 50Hz Lamp 240V 10W E 12 Lamp socket 250V 1A E 12 Hard plastic body type F thermostat MM1 8038 ON 20 C OFF 25 C Defrost heater MM1 4021 220 230 240V 378Ω with deodorizer Compressor FL1568SZ 220 230 240V 50Hz Mai...

Страница 7: ... A Compressor Starting Relay B B P P W Defrost Thermo P R Door Switch F Door Switch O S B Lamp Fan Motor Br Br F Thermostat R W Thermo Fuse Bk Defrost Heater Defrost Timer Protector CONNECTED IN TERMINAL BOX CONNECTOR Plug Cord 2 3 1 B Bk Br G O S B P R W Y BLUE BLACK BROWN GRAY ORANGE SKY BLUE PINK RED WHITE YELLOW 1 2 3 4 1 2 B G Figure W 1 Wiring Diagram ...

Страница 8: ...1 2 3 4 5 6 1 2 3 1 2 3 3 2 4 1 TM L Defrost Timer Compressor C M A Starting relay F Door Switch C2 3P 110V C6 SGF 21T 5 W 2 C7 SGF 21T 5 W 3 1 1 Protector Terminal cover Plug Cord Tube Tube Tube 2 2 P 2 O 1 R 1 Bk 1 G 2 P 1 S B 1 Br 2 G 1 W 2 C3 LR 09 1V C5 LR 06 1V W 2 1 2 3 R Door Switch C4 3P 110V B 2 P 2 1 2 3 S B 1 Tube CE 2 Br CE 2 B CE 2 G FREEZER REFRIGERATOR MACHINE ROOM Food liner RC bo...

Страница 9: ...trol sets to the CHILLED ZONE some foods stored may freeze In this case adjust control set back to the MED position When refrigerator temperature control sets to the CHILLED ZONE some foods stored in fresh cases may also become frozen The values shown above refer to the measurement carried out center area and 1 3 of overall height from the bottom at each of the refrigerator and the freezer after m...

Страница 10: ...the operation time delay time of defrost timer defrosted water is drained outside the refrigerator Timer contact is changed to cooling operation and the compressor starts running and the timer motor stops Defrost thermostat contact becomes ON when it s cooled And the timer moter starts running Figure F 4 Figure F 4 Figure F 5 Figure F 6 Figure F 7 TM COMP Defrost thermostat ON Compressor running T...

Страница 11: ...elt hot if touched by hand while the compressor is in operation If you are asked about this please explain that the hot pipe serve to prevent the dew generation Figure F 8 4 INSPECTION OF INITIAL STARTING 1 Inspection of cooling unit 1 Set the temperature control knob to MAX and check that the compressor starts to operate 2 Depress the door switch to run the fan and check that cool air is blown ou...

Страница 12: ... catalyst consists of zeolite alumina silica noble metal and rare earth oxide It adsorbs and decomposes the following odors It adsorbs Stench odor evolved from vegetables and fruits Methyl mercaptan Stench odor evolved from meats and fishes Trimethylamine Stench odor evolved from fermentation foods Aliphatic acids The noble metal and rare earth oxides act as catalysts which oxidize and remove the ...

Страница 13: ... Seal the slit with paper tape 3points 1 Sticking of E V cover sealer A B Lead E V cover ass y Fan motor holder B Motor cushion Motor cushion Fan motor Fan motor holder A Dofrost thermo ass y L band C E V cover sealer C E V cover sealer D E V cover sealer A Paper tape E V cover E V cover sealer B Aluminum tape L band C Paper tape Thermo fuse ass y SL 5N clip Propeller fan 100 Fan clamp L band C F ...

Страница 14: ...Motor cushion 2 2 mm 2 2 mm Fan motor cushion B D D Motor cushion Sec DD Motor cushion Motor cushion Fan motor cushion A Fan motor cushion B Fan motor Check claw is surely fixed to the hole of Fan motor cushion Fan motor Lead wire Insert terminal of Lead wire Orange and Gray to the terminal of Fan motor Lead ev cover ass y has positive lock ...

Страница 15: ...rmostat Defrost thermo ass y L band C Thermo sensing element side Horizontally E No good Within 30 Cut off to 7mm or shorter View from E SL 5Nclip Thermo fuse ass y Lead wire WHITE Lead wire WHITE SL 5Nclip Thermo fuse ass y Aluminum tape 50 m X 70mm X 130mm Take out lead wire from square hole to front and seal with E V cover sealer D Set lead wire at right side of the hole See from rear But only ...

Страница 16: ...g of Fan Set Fan clamp to Propeller fan 100 and insert it to the shaft of Fan motor E V cover Propeller fan 100 More than 3mm Shaft 1 1mm Slit of each Fan clamp and Propeller fan should not be at same position Fan clamp Slit 1 4 7 2 5 8 3 6 9 No 3 Pink lead of Defrost thermo ass y No 4 Blue lead of Defrost thermo ass y No 7 Black lead of Thermo fuse ass y No 8 White lead of Thermo fuse ass y ...

Страница 17: ...SKY BLUE inserted in No 5 BROWN inserted in No 6 D timer lead ass y 1 2 3 4 5 6 7 8 9 Lamp 5 2mm Nylon band rib a R C box cover screw Lamp socket Defrost timer Nylon band rib a Warning label R C box cover 1mm Warning label Lamp socket Lamp Defrost timer D timer lead ass y WARNING 5 2mm ...

Страница 18: ...y for SJ V35L Back condenser Figure C 1 Figure C 3 Figure C 2 Cooling unit Location Capillary tube Dryer Charge pipe Charge pipe L Suction pipe Evaporator Compressor Back condenser Sub condenser ass y Hot pipe Dryer Hot pipe outlet Charge pipe L Charge pipe Capillary tube Sub condenser Back condenser Pinch point Hot pipe inlet Nylon band Sub condenser Suction pipe ...

Отзывы: