AYZP40KR
4 – 1
AYZP40KR
Service Manual
CHAPTER 4.
REFRIGERATION CYCLE
[1] SCHEMATIC DIAGRAM
[2] STANDARD CONDITION
* REFRIGERANT PIPE LENGTH 5m
[3] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE
* On test run mode
[4] PERFORMANCE CURVES
NOTE
1) Indoor fan speed: Hi
2) Vertical adjustment louver "front”, Horizontal adjustment louver "level"
3) Indoor air temp. : Cooling 27
C, Heating 20
C
4) Power source : 230V, 50Hz
5) Compressor speed : Rated frequency
Indoor side
Outdoor side
Dry-bulb Temp. (
C)
Relative Humidity (%)
Dry-bulb Temp. (
C)
Relative Humidity (%)
Cooling
27
47
35
40
Heating
20
–
7
87
Model
EHP6.0AA/I-O
NO. Condition
Cooling
Heating
Temp. on
(
C)
66
59
Temp. on
(
C)
38
3
Temp. on
(
C)
13
25
Temp. on
(
C)
16
5
3-way valve pressure (MPaG)
1.0
2.2
s
1
4
C
2
Accumulator
3
Strainer
Expansion
valve
Heating
Cooling
Outdoor unit
Condenser
Evaporator
Indoor unit
Reverse valve
Comp-
ressor
Flare coupling
Flare coupling
3-way
valve
2-way
valve
Silencer
Coil
s
Strainer