background image

SIM425-002 

 

 

 

 

3

 

operating load. 

13.

 

Do not work alone (always work as a team of 2 or more people). 

14.

 

Wear a safety harness when working above the ground. 

15.

 

Do not wear metallic jewelry which may conduct electricity and enable 
electric shock during installation. 

16.

 

Do not damage the back sheet of PV modules when fastening the PV 
modules to a support by bolts. 

17.

 

Do  not  damage  the  surrounding  PV  modules  or  mounting  structure 
when replacing a PV module. 

18.

 

Use  UV  resistant  cable  ties  or  other  wire  management  hardware  to 
secure  the  interconnect  cables.  Drooping  cables  may  cause  various 
problems, such as leading to electrical shorts. 

19.

 

Take  proper  measures  for  preventing  the  laminate  (consisting  of 
encapsulant,  cells,  glass,  back  sheet,  etc.)  from  dropping  out  of  the 
frame in case the glass is broken. 

20.

 

Cables  shall  be  located  so  that  they  will  not  be  exposed  to  direct 
sunlight in order to prevent degradation of the interconnect cables. 

21.

 

Do not cover the water drain function of the frame. There might be a 
risk of frost damage when the hollow portion of the frame is filled with 
water cumulation. 

 

4. SITE SELECTION 

In  most  applications,  the  PV  modules  should  be  installed  in  a  location 

where there is no shading throughout the year. In the Northern Hemisphere, 
the  PV  modules  should  typically  face  south,  and  in  the  Southern 
Hemisphere, the PV modules should typically face north. 

Please  make  sure  that  there  are  no  obstructions  in  the  surroundings  of 

the site of installation. TAKE PROPER STEPS in order to maintain reliability 
and safety, in case the PV modules are used in areas such as: Heavy snow 
areas / Extremely cold areas / Strong wind areas / Installations over, or near, 
water / Areas where installations are prone to salt water damage/corrosive 
gas environment/ Small islands or desert areas. 

The  results  of  the  ammonia  test  and  the  salt-mist-corrosion  test  on  the 

modules,  carried  out  under  such  strict  test  conditions,  should  be  disclosed 
for  reference  purposes  only.  The  decision  on  whether  the  modules  are 
suitable and compatible for each installation field will depend on the user’s 
judgement and responsibility. 

 

5. TILT ANGLE SELECTION 

The tilt angle of the PV module is measured between the surface of the PV 

module  and  a  horizontal  ground  surface.  The  PV  module  generates 
maximum output power when it faces the sun directly. 

5 degrees or more is recommended for the tilt angle of the PV module for 

the maintenance. (See 9. Maintenance) 

For standalone systems with batteries where the PV modules are attached 

to  a  permanent  structure,  the  tilt  angle  of  the  PV  modules  should  be 
selected to optimize the performance based on seasonal load and sunlight. 
In general, if the PV output is adequate when irradiance is low (e.g., winter), 
then the angle chosen should be adequate during the rest of the year. For 
grid-connected  installations  where  the  PV  modules  are  attached  to  a 
permanent  structure,  PV  modules  should  be  tilted  so  that  the  energy 
production from the PV modules will be maximized on an annual basis. 

 

6. ELECTRICAL INSTALLATION 

(INCLUDING WIRING & GROUNDING) 

To ensure proper system operation and maintain the guaranty, be careful 

to observe the correct cable connection polarity (Figure 1) when connecting 
the modules to a battery or to other modules. If not connected correctly, the 
bypass diode(s) could be destroyed. 

 
 
 
 
 
 
 
 
 
 
 
 

 
# Maximum series configuration: please refer to Table-1  

(This value is calculated under the condition of Voc at - 40 °C.)  

# Maximum parallel configuration: Parallel connection of each string shall 

be conducted with following two options. Any other parallel connections 
are prohibited. 

       a) Case of using the diodes; 1 diode per maximum 2 parallel strings 

(Connet a diode or more in series for every string or every 2 parallel 
strings for protection of module from reverse current over load.)  

b) Case of using the fuses; 1 fuse per every string (Connect a fuse for 

every single string for protection of module from reverse current over 
load.)  

All PV modules must be grounded by electrical connection of the module 

frames to ground. Care must be taken to arrange the system ground so that 
the removal of one module from the circuit will not interrupt the grounding of 
any of the other modules. 
 

Cable characteristics 

Cable size :     

12 AWG (4.0mm

2

)  

Rating temperature: 

-40

°

C to +90

°

C (-40

°

F to +194

°

F) 

 

Grounding 

The frame grounding must consider the local requirement and regulation at 

the  installation  site.  When  grounding  is  required,  please  refer  to  below 
example connection (Figure 2).  Please be careful in arranging the system 
ground so that the removal of one module from the circuit will not interrupt 
the grounding of any other modules. 

 
 
 
 
 
 
 
 

For grounding, each PV module has a hole in the frame with the appropriate 
symbol  for  either  a  bolt,  nut  and  washer,  a  ground  lug  fastened  by  bolt  or 
screw, or an appropriate screw (hardware not provided). In a connection of 
this  type,  the  hardware  (such  as  a  star  washer)  must  score  the  frame 
surface to make positive electrical contact with the frame. The ground wire 
must  be  considered  within  the  local  requirement  of  local  and  regulation  at 
the site of installation. 
 

( for US market )

 

Installation for wiring shall be in accordance with the NEC and grounding 

method shall comply with the NEC, article 250 and the relevant instructions 
below.  In  a  connection  of  this  type,  the  hardware  (such  as  a  star  washer) 
must  score  the  frame  surface  to  make  positive  electrical  contact  with  the 
frame. The ground wire must not be smaller than No.12 AWG (Insulated for 
90  degree  C  Min.)  and  can  be  insulated  with  green  colored  insulation  or 
insulated with green with yellow stripe(s) insulation. The ground wire should 
be sized according to the NEC and other laws.  

If  modules  are  installed  in  a  readily 

accessible location (per NEC) where the 
circuit is operating in excess of 30 volts, 
nominal,  maximum  system  voltage  for 
DC  or  30  volts  for  AC  circuits,  NEC 
requires  installing  the  additional  locking 
sleeve  connector  (Multi  Contact  #PV-
SSH4,  see  Figure  3)  on  the  connector. 
Note that this sleeve is not included with the module. 

 

Where common grounding hardware (nuts, bolts,  star washers, spilt-
ring lock washers, flat washers and the like) is used to attach a listed 
grounding/bonding  device,  the  attachment  must  be  made  in 
conformance with the grounding device manufacturer's instructions.  

 

Common  hardware  items  such  as  nuts,  bolts,  star  washers,  lock 
washers  and  the  like  have  not  been  evaluated  for  electrical 

 

SERIES WIRING (VOLTAGE ADDITIVE) 

Figure 1 

PARALLEL WIRING (CURRENT ADDITIVE) 

Figure 2.  Example of acceptable ground connection 

Additional locking sleeve 

Figure 3 (MC; PV-SSH4) 

Содержание NU-SA Series

Страница 1: ...se the lower edge of the module frame to deform Take necessary measures e g snow stopper to avoid possible damage 14 Periodically remove any overhanging snow and or ice from the module framework as it may cause deformation of the module frame GENERAL INSTRUCTIONS 1 INTRODUCTION Thank you for choosing SHARP photovoltaic PV module This Installation Manual contains essential information for the elect...

Страница 2: ...ent for US market only 16 When installing PV modules in a readily accessible location the National Electrical Code NEC 690 33 requires installing the additional locking sleeve Multi Contact part PV SSH4 on the connector Note that this sleeve is not included with the module This requirement is for circuits operating in excess of 30 volts nominal maximum system voltage for DC or 30 volts for AC circ...

Страница 3: ...igure 1 when connecting the modules to a battery or to other modules If not connected correctly the bypass diode s could be destroyed Maximum series configuration please refer to Table 1 This value is calculated under the condition of Voc at 40 C Maximum parallel configuration Parallel connection of each string shall be conducted with following two options Any other parallel connections are prohib...

Страница 4: ...re mounted on should be rigid SHARP PV modules are designed to ensure optimal electrical performance under the condition that they are mounted on rigid support structures Deformation of support structure may damage PV module with its electric performance When mounting the module on structure ensure that no corner has a displacement of more than 2mm 0 08in per every 1000mm 39 37in of the diagonal f...

Страница 5: ... fuse sizes and size of controls connected to the module output for US market Refer to Sec 690 8 of the National Electric Code for an additional multiplying factor of 125 percent 80 percent de rating which may be applicable Application Class This module is rated as Application class A according to IEC61730 Application class A means General access hazardous voltage hazardous power applications Modu...

Отзывы: