15
AH-S327W2
AU-S327W2
1-11
Compressor relay RY1
(1) It is ON during operation, and when operation is
stopped, goes OFF after a delay of 100 seconds
(not immediately).
(2) The minimum OFF time of the relay is 80 seconds.
It will not go ON again before 80 seconds elapses.
ON
OFF
OFF
Air conditioner
operation
Compressor
relay
100 sec.
ON
(3) If air conditioner operation is turned on again during
the 100 seconds delay before the compressor relay
goes off, the compressor relay will stay on.
ON
OFF
ON
ON
Air conditioner
operation
Compressor
relay
100 sec.
ON
ON
OFF
ON
OFF
Air conditioner
operation
Compressor
relay
100 sec. 80 sec.