3 – 6
To measure the resistance, first remove the connector from the board.
2. How to distinguish the defective parts
1. When all rooms are not cooled
Thermistor
No.
Connector
Color
Connector pin
Compressor thermistor
TH1
CN8A
Red
No. 1 to 2
Heat exchanger pipe thermistor
TH2
CN8A
Orange
No. 3 to 4
Outdoor temp. thermistor
TH3
CN8A
Green
No. 5 to 6
Suction thermistor
TH4
CN8A
Black
No. 7 to 8
Thermistor unit A (suction)
TH6
CN8C
Blue
No. 1 to 2
Thermistor unit B (suction)
TH7
CN8C
White
No. 3 to 4
500
400
300
200
100
0
-20
0
20
40
Temperature (ºC)
80
100
3.25k
60
12.3k
6.14k
Resistance
(k
)
Thermistor
Heatsink
Color
Black
To measure the resistance, first remove
the connector as shown at right.
Signal
CN8B
Heatsink thermistor
TH5 (black)
25ºC resistance 50k
Tester
1
3
Figure 3 Temperature properties of heatsink thermistor
Yes
Yes
Yes
No
No
No
Are the timer lamps of the in-
door units in all rooms flashing ?
Is the compressor of the outdoor
unit operating ?
Are the timer lamps of the indoor
units in all rooms flashing ?
Check the failure symptom with
the failure diagnosis mode.
The cooling cycle is abnormal.
Check the pressure.
Check that the power between
the terminal board " N " and " 1 "
of the indoor unit is AC 230V,
50Hz.
Repair the wiring between the
units.
Press the OPERATION button
to start operating the air-condi-
tioner. (One-room operation ON)
(Set the cooling mode to 18ºC)
(Check the failure with
the outdoor unit.)
TO
A
Содержание AE-X2M14LR
Страница 32: ...AEX2M14LR 5 6 MEMO ...