26
AY-XP08/10/13CE
AE-X08/10BE-C
AE-X13BE
2-6 Power factor module
(AE-X08BE-C / AE-X10BE-C)
If a voltage error (over 400 V), current error (over 17 A), or temperature error (over 90°C) is detected in the power
factor module, 170 seconds the compressor is stopped.
(AE-X13BE)
If a voltage error (over 420V) is detected at power factor module output voltage, 170seconds the compressor is
stopped.
In this case, the outdoor fan does not stop, and 170 seconds after operation is stopped, another try will be made.
Three retries are allowed. On the fourth retry, a complete stop request signal is sent to the indoor unit, and the
outdoor unit will remain stopped until reset is performed. At this time, the 3-minute delay for control of the outdoor
unit will not function; therefore, do not cancel by removing the plug and cutting the power.
2-7 Serial signals
(1) Serial signals consist of all 96-bit signals.
(2) If the outdoor unit does not receive a serial signal, it will stop approximately 30 seconds later. Note that this is true
only of normal operation; in test mode, it does not stop and operation takes place based on the test mode
commands.