8.2.8 RL2 THRESHOLD
Press ENTER to display the previous setting. Set the distance from the sen-
sor
Use SCROLL and UP ARROW to modify the value; in the example the RL2
min. level threshold distance is 3000mm.
Press ENTER to confi rm.
NB - RL2 inactive with 0000mm
METER -
quick setup
SET DISTANCE 4mA
SET DISTANCE 20mA
MEDIUM
FILTER COEFFICENT
BLIND DISTANCE
DISPLAY
RL1 THRESHOLD
RL2 THRESHOLD
►
3000 mm
RL2 THRESHOLD
Level
SET
RL2 “ON”
RL2 “OFF”
RL2
RL2
RL2
RL2
RL2
RL2
RL2
RL2
Min.
Alarm
Min.
Alarm
M
in. lev
el
alarm z
one
3000mm.
METER
reference point
RL2 THRESHOLD
RL2, MIN. LEVEL ALARM
HYSTERESIS
When confi rming with the ENTER button the maximum level threshold value storage, in the example 3000mm
the METER activates RL2 with the following default settings for level alarm threshold:
1) MIN / MAX = MIN; minimum level alarm
2) DELAY = 0 sec.; no switching delay
3) SECURITY = YES; relay de-energized, and contact open, during the maximum level alarm
4) ENABLE / DISABLE = ENABLE; alarm threshold function enabled
5) MIN/MAX HYSTERESIS mm = 40mm
To change these relay settings is necessary to access the advanced setup menu and any subsequent changes
to the RL2 threshold value not affect the relay custom settings.