background image

15

The floating switches have to close when they are floating on the surface. The floating switches 

have to be connected floatingly. The required signal voltage is generated in the control system and 

amounts to 5V.

Assignment of the float switches:

SWN1 = pump off
SWN2 = pump on
SWHW = high water alarm
 

For the usage in explosion-prone areas, either floating switches with the 

corresponding permission, or intrinsically safe cut-off relays have to be 

used. 

The external sensor has to supply a measurement current between 4 

and 20mA. The final value of 20 mA can be adjusted in the menu, so the 

indication may occur in cm.

3.2.5 Utilisation of the internal sensor

A pressure sensor of 0 to 10 kPa is used as an internal sensor (0 to 1mWs, 0 to 100 mbar). Other 

measurement ranges can be realised on demand. On the lower side wall, a hose screw connection 

6/8mm is located which is intended for the connection of the immersion pipe. The sensor used 

is designed as a differential pressure converter, so that barometric variations are eliminated. The 

menu item “internal converter – adjustment” serves for the accurate adjustment of the zero point.

In order to equalise possible air leaks inside the pneumatic level 

measuring device, the pilot tube has to be fully emerged from the water 

after completion of the pumping process. For this purpose, the adjustment 

of a follow-up time of the according duration is necessary. Alternatively, 

the small-size compressor set for the air bubbler level measurement 

system can be used. 

3.2.6 Signal contacts

The 4 potential-free signal contacts are located in the upper circuit board (left). 
The 4 signal contacts are free and programmable: the contacts 1 and 2 are opened in case of 

power failure and the contacts 3 and 4 are closed in case of power failure.
If the power supply of the control is correct, then the signal contacts are closed in case of a fault 

or signal.

3.3 Commissioning of the control system

After the complete connection of the pump cables, the mains power supply and the level sensor, 

the parameters can be set after the mains voltage has been applied. Only trained personnel are 

allowed to set those parameters.
Now the plant can be commissioned by pressing the key 

. During the conduction of several 

test runs, the set switch points have to be checked, and, if necessary, corrected.

    

  

    

  

    

  

    

  

Содержание ZPS 1.3

Страница 1: ...Electronic pump control Operation and assembly instructions CONTROL BOX ZPS 1 3 9001 3 11 19...

Страница 2: ...English 3 Deutsch 17 Fran ais 32 Italiano 47 Nederlands 62 Espa ol 76 Portugu s 91...

Страница 3: ...l characteristics pg 5 2 3 Technical data pg 5 3 OPERATION OF THE CONTROL SYSTEM pg 6 3 1 Operator control panel and operational elements pg 6 3 1 1 Key pg 6 3 1 2 Indications on the display pg 7 3 1...

Страница 4: ...ce of at least 3 mm The connection must be used exclusively to provide the power to the product If the power cord is damaged to prevent possible danger it must be replaced by the manufacturer customer...

Страница 5: ...istics Clear LCD display Hand Stop Auto Function 1 acknowledgement button 2 parameter select buttons Menu which can be switched through Internal acoustic alarm Programmable operation and collective fa...

Страница 6: ...y pressing this key the preferred pump is switched on without delay No other function of the program is enabled The green LED of one pump flashes ATTENTION If the ATEX mode is enabled the pump can onl...

Страница 7: ...re displayed alternately In case of failure the actual failure status is displayed see point 3 1 6 The red LEDs of the pump will be seen red flashing light Parameter setting In the upper line the desi...

Страница 8: ...sensor Flooding alarm level Additionally this level is constantly evaluated on the input for the floating switch HW independent from the selected level transmitter Thereby if necessary 2 different HV...

Страница 9: ...efly started if no request occurs by the switch on level within 24 hours If the ATEX mode is enabled the 24h starting is only taking place if the turn off level is exceeded acoustic alarm is activated...

Страница 10: ...via external sensor intern converter matching calibration By pressing the key sequence the zero point of the internal converter is adjusted The adjustment has to be carried out while the pilot tube i...

Страница 11: ...maintenance within days XXXX in days Shows the number of days until the next maintenance The information is saved at intervals of 4 hours The initial value can be preset between 365 and 0 days 3 1 6...

Страница 12: ...anually Yes Pump TH1 TH2 Phase error A phase of the power supply has failed Yes Dreh Fault ATEX The ATEX mode is activated and the level is below the switch off point of the selected pump Yes Atex Run...

Страница 13: ...rding to the connection diagram shown below Connection of a 3 phase Motor Connection of a single phase Motor with internal capacitor Mains connection Pump1 Protective conductors Mains connection Pump1...

Страница 14: ...t board The active sensor can be selected in the menu level control and therm malfunction If the thermostatic switch TH2 is not necessary a bridge has to be inserted on this contact point The thermost...

Страница 15: ...verter adjustment serves for the accurate adjustment of the zero point In order to equalise possible air leaks inside the pneumatic level measuring device the pilot tube has to be fully emerged from t...

Страница 16: ...idge thermal contacts TH2 5 Disable thermic error for the pump If the respective level sensors are connected all program functions can be checked without having to connect the pump 4 DISPOSAL Only for...

Страница 17: ...Contact Information SFA Australia Pty Ltd Unit 10 25 Gibbes Street Chatswood NSW 2067 Phone 1300 554 779 E GENERAL ENQUIRIES info saniflo com au E TECHNICAL SUPPORT technical saniflo com au...

Отзывы: