24
Operating Instructions – MOVITRAC® LTP
5
Optical interface
Electrical Installation
5.3
Optical interface
The optical interface, which is located next to the RJ11 connector, is mainly used for
commissioning and monitoring the drive with a pocket PC. When LTP shell CE is
installed, the pocket PC can be used to commission the drive and monitor the current
status of the drive.
5.4
UL-compliant installation
Note the following for UL-compliant installation:
• The drives can be operated within an ambient temperature of 0 ... 50 °C.
• Only use copper connection cables which can withstand ambient temperatures of up
to 75 °C.
• Permitted tightening torques for MOVITRAC
®
LTP power terminals are:
– Sizes 1, 2 & 3
= 1 Nm / 8.9 lb.in
– Size 4
= 4 Nm / 35.4 lb.in
– Sizes 5 & 6
= 8 Nm / 70 lb.in
MOVITRAC
®
LTP drive inverters are suitable for operation in voltage power systems
with an earthed star point (TN and TT systems), which can supply a maximum supply
current and a maximum supply voltage in accordance with the following table. The fuses
listed in the following tables are the maximum permitted fuses for each inverter. Only
use melting fuses.
Only use tested units with a limited output voltage (V
max
= DC 30 V) and limited output
current (I = < 8 A) as an external DC 24 V source.
UL certification does not apply to operation in voltage supply systems with a non-earthed
star point (IT systems).
5.4.1
200 ... 240 V Units
MOVITRAC
®
LTP...
Short circuit rating
Max. supply voltage
Fuses
0004
AC 5000 A
AC 240 V
AC 6 A / 250 V
0008
AC 5000 A
AC 240 V
AC 10A / 250 V
0015
AC 5000 A
AC 240 V
AC 20A / 250 V
0030, 0040, 022
AC 5000 A
AC 240 V
AC 32 A / 250 V
0055
AC 5000 A
AC 240 V
AC 50 A / 250 V
0075
AC 5000 A
AC 240 V
AC 80 A / 250 V
0110, 0150
AC 5000 A
AC 240 V
AC 100 A / 250 V
0185
AC 5000 A
AC 240 V
AC 125 A / 250 V
0220
AC 10000 A
AC 240 V
AC 160 A / 250 V
0300
AC 10000 A
AC 240 V
AC 200 A / 250 V
0370, 0450
AC 10000 A
AC 240 V
AC 300 A / 250 V
0550
AC 10000 A
AC 240 V
AC 350 A / 250 V
0750
AC 10000 A
AC 240 V
AC 400 A / 250 V
0900
AC 10000 A
AC 240 V
AC 500 A / 250 V