90
Operating Instructions – MOVIGEAR® SNI-B
5
Assignment of optional plug connectors
Electrical installation
5.10 Assignment of optional plug connectors
5.10.1 X1241_1 and X1241_2: AC 400 V connection with SNI
The following table shows information about this connection:
WARNING
Electric shock when disconnecting or connecting voltage-carrying plug connectors.
Severe or fatal injuries
• Switch off the power supply voltage.
• Never plug or unplug plug connectors while they are energized.
Function
AC 400 V connection for supplying the unit/for looping through
With Single Line Network Installation (SNI)
Connection type
M23, SEW insert, SpeedTec equipment, Intercontec, female, coding ring: red, protected against contact
Wiring diagram
2497125387
Assignment
No.
Name
Function
A
L1_SNI
Actuator supply phase L1 with SNI communication
B
L2_SNI
Actuator supply phase L2 with SNI communication
C
L3_SNI
Actuator supply phase L3 with SNI communication
D
n.c.
Not connected
PE
PE
PE connection
1
n.c.
Not connected
2
n.c.
Not connected
3
n.c.
Not connected
4
n.c.
Not connected
5
n.c.
Not connected
6
n.c.
Not connected
7
n.c.
Not connected
8
n.c.
Not connected
9
n.c.
Not connected
10
n.c.
Not connected
SHLD
n.c.
Not connected
A
6
4
5
PE
B
C
D
SHLD
1
2
3
INFORMATION
The communication method requires that you must observe the order of the line
phases L1, L2, L3 between SNI controller and SNI stations 1 to 10.