Electrical Installation
Installation instructions (all versions)
32
Operating Instructions – MOVIFIT
®
SC
6.2.4
Notes on PE connection and/or equipotential bonding
Earth-leakage currents
Ã
3.5 mA may occur during normal operation. To conform to
EN 61800-5-1, observe the following:
• Route a second PE conductor with the cross-section of the mains lead in parallel to
the protective earth via separate terminals or use a copper protective earth with a
cross-section of 10 mm
2
.
6.2.5
Definition PE, FE
• PE refers to the mains-side protective earth connection. The PE conductor in the
mains connection cable may only be connected with terminals marked with "PE"
(these are designed for the maximum permissible mains connection cross-section).
• FG refers to connections for "functional ground". You can connect any existing
grounding conductor in the 24 V connection cable. Caution: Do not connect the
mains-side PE. These connections are not designed for this purpose and so elec-
trical safety is not guaranteed.
DANGER
Faulty PE connection
Severe or fatal injuries or damage to property from electric shock.
• The permitted tightening torque for the fitting is 2.0 to 2.4 Nm (18...21 lb-in).
• Observe the following notes regarding PE connection:
Prohibited assembly
Recommendation: Assembly with forked
cable lug
Permitted for all cross-sections
Assembly with thick connecting wire
Permitted for cross-sections up to
max. 2.5 mm
2
57461AXX
57463AXX
60800AXX
[1] Forked cable lug suitable for M5 PE screws
[1]
M5
2.5 mm²