5
Electrical installation
Connection via hybrid cable
Operating Instructions – MOVITRANS
®
TPM12B Mobile Converter, System Frequency A – 25 kHz
28
5.5.2
Cable cross section
The following illustration shows the cross-section of the open cable end:
0V 500
500 V OK
BK
L1
BK
L2
WH
0V
RD
24V
WH
0V
BK
L3
GNYE
0V 24
24 V
500 V
PA
GN
RS-
OG
RS+
[1]
[2]
1520642187
[1]
Enable mode
[2]
Enable
5.5.3
Assignment
The following table shows the assignment of the wires:
Device connector
Designation
Hybrid cable
X11:A1 +U
z
500 V
L1
X11:A2 -U
z
0V500
L2
–
–
L3
X11:B1
X11:B2
X11:B3
X11:B4
X11:B5
X11:B6
X11:B7
X11:B8
PA
n.c./not connected
Enable mode
0V24
PA
500 V OK
Enable
24 V auxiliary voltage
GNYE
-
WH
WH
Shield
Upper limit
GN
RD
Observe the following:
•
CAUTION!
Do not apply external voltage to the terminal "500 V OK".
•
Strand L3 of the hybrid cable must not be connected.
•
The terminals "Enable" and "Enable mode" only affect the DC 500 V output
voltage. The DC 24 V voltage output is not affected.
23613653/EN – 01/2018