5
Electrical installation
Protective measures against electrical hazards
Operating Instructions – MOVITRANS
®
TPM12B Mobile Converter, System Frequency A – 25 kHz
19
5.3
Protective measures against electrical hazards
5.3.1
Overview
The following figure shows an overview of preventive measures against electrical haz-
ards:
Stationary use
Protective measures in accordance with IEC 60364-4-41
Mobile use
Contactless energy transfer system
Ground connection
Protective
separation
ESD protection
Contactless energy transfer system
9007216786656779
5.3.2
Contactless energy transfer system
The following preventive measures protect mobile systems with contactless energy
transfer against electrical hazards:
•
Protective separation
•
ESD protection
Protective separation
Comply with "preventive separation" in line with VDE 0100 part 410 nominal voltage
< 500 V by using the following measures:
•
All electrical equipment on the mobile part, such as on a vehicle, must be equipo-
tentially bonded to each other.
•
Establish high-frequency equipotential bonding via the vehicle support frame
(vehicle GND).
•
All cables must have double basic insulation. This requirement is always met when
using MOVITRANS
®
components.