Manual – MOVIPRO® SDC with DeviceNet Interface
115
10
Explanation of the parameters
Parameterization of MOVIPRO
®
10.4.9 P8xx Unit functions
P80x Setup
P802 Factory set-
ting
Setting range: No / standard / delivery condition
You can use P802 to reset the factory settings stored in the EPROM for almost all pa-
rameters.
• The following data are not reset when "Standard" is selected:
– Application module
–
P20x Speed control
(page 95)
–
P210 P gain hold controller
(page 98)
–
P30x/P31x Limits 1/2
(page 98)
–
P32x/P33x Motor compensation 1/2
(page 100)
–
P344 Motor protection interval
(page 103)
–
P345/P346 I
N
-U
L
monitoring 1/2
(page 103)
–
P53x Motor temperature protection
(page 105)
–
P70x Operating modes
(page 109)
–
P73x Brake function
(page 112)
–
P905 Hiperface offset (motor)
(page 124)
–
P910 Gain X controller
(page 124)
–
P94x IPOS encoder
(page 129)
–
Fault memory
–
Statistical data
• The "Delivery condition" setting also resets the data listed above.
"8.8.8" appears on the 7-segment display during the reset. The previous operating sta-
tus of the inverter appears on the display after the factory settings have been restored.
P802 automatically reverts to "No".
INFORMATION
The "Standard" setting overwrites almost all parameter values; the setting "Delivery
condition" overwrites all parameter values. Save the set parameter values with
MOVITOOLS
®
Motion-Studio before you start resetting the parameters. After reset-
ting, it is necessary to adapt the altered parameter values and terminal assignments
to meet the requirements.