3
Electrical installation
Control connections
Addendum to the Operating Instructions – MOVIDRIVE
®
MDR60A1320-503-01 regenerative power supply
13
Terminal
Function
Description
X2:1 NC contact
Isolated relay contacts
1)
and there is
no collective fault, the relay picks up.
2)
Collective fault signal switching capacity of the
relay contacts:
•
30 V DC 3 A
•
230 V AC 5 A
X2:2 NC contact
X2:3 NO contact
X2:4 NO contact
X2:5
Internal assignment for temperature
monitoring
X2:6
X2:7
OFF pushbutton
To switch off the regenerative power supply
X2:8
X2:9
Not assigned
X2:10
X2:11 (+24 V)
External voltage input
To switch on the regenerative power supply or
confirm faults
X2:12 (0 V)
1) When the supply voltage is present, the precharging of the DC link capacitors is complete,
2) The relay drops out in the event of an OFF command via terminals X2:7 and X2:8 and in the event of a fault message.
3.2.5
Terminal assignment inhibit input A1/A2
Terminal
Function
Description
A1
Inhibit input 24 V
Control voltage to inhibit the regenerative
power supply path (not isolated)
A2
DGND
Higher-level
controller
Binary output
MOVIDRIVE
MDR60A1320-503-01
®
DGND
A1
A2
9007203321273099
3.3
Control connections
Use the terminal control strip X2 to connect via relay certain messages such as ready
for operation or a collective fault outside the unit. You can also perform an external
RESET or switching function via the control terminal strip X2 and link it with the fre-
quency inverter.
27789314/EN – 07/2022